Diagnostic and error messages

Video Recorder – User Manual

257

Table 9-4 Error Messages (continued)

Error

Description

User Action

Low Limit Outside of
Circuit

AI circuit low limit is < voltage limit of -500 mV.

Change circuit low limit to > -500
mV.

Low limit Outside of
Table

For thermocouple or RTD, Range Low limit is < the
low limit for that type.

Change limit to within specified
limits for that type. (Table 4-3)

Low Output Limit less
than Zero

A current output (CAT) low limit is less than zero.

Change current output (CAT) low
limit to greater than or equal to
zero.

Monthly Periods Must Be
Phased

Periodic Timer CV period is monthly but no phase is
defined.

Change Periodic Timer phase.

No Room for Function
Block

System has used all allocated function blocks.

Verify programming of affected
function block.

Number of Frames Out of
Range

Rolling Average CV # of Samples is less than 1 or
greater than 60.

Change # of Samples to 1-60.

Out of EEPROM Memory

No more static memory or EEPROM memory.

Verify programming of affected
function block.

Out of RAM Memory

No more RAM available.

Verify programming of affected
function block.

Output Limits Equal

Output (range) limits (low and high) must be unequal.

Change to unequal limits

Pairs Inconsistent

Applies to custom AI or Function Generator CV.
Curve has Xn but no Yn or vice versa. Curve does
not have at least 2 X,Y pairs.

Program a Y for each X or vice
versa. Program at least 2 X’s and
2 Y’s.

Request Made with
Invalid Tag

Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.

Verify programming of affected
function block.

Requires a Deviation
Parameter

Deviation alarm does not contain deviation.

Program alarm with deviation.

Requires Input
Parameter

Alarm does not contain an input.

Program alarm with input.

Requires Setpoint
Parameter

Alarm does not contain a setpoint.

Program alarm with a setpoint.

RJ Not in Curve

AI is custom type, class thermocouple, RJ enabled
but curve does not contain 0-65 degrees C (32-149
degrees F).

Y values must contain 0-65
degrees C (32-149 degrees F).

Temperature Constant
Not Programmed or Less
Than Zero

F0 Sterilization CV Temperature constant is not
programmed or is less than zero.

Program Temperature constant
with value greater than or equal to
zero.

Temperature Input Not
Programmed or Less
Than Zero

F0 Sterilization CV Temperature Input is not
programmed or is less than zero.

Program Temperature input with
value greater than or equal to
zero.

Temperature Reference
Not Programmed or Less
Than Zero

F0 Sterilization CV Reference Temperature is not
programmed or is less than zero.

Program Reference Temperature
with value greater than or equal to
zero.