Programming and Operating Concepts

Video Recorder – User Manual

71

AI1

TYPE J

THERMOCOUPLE

AI1 OV

INPUT TYPE = J

RANGE LOW = 0

RANGE HIGH = 1000

LP1

PV

LP1 OV

TYPE = STANDARD

SP1 = 500

SP2 = SP1 OV

GAIN = 10

RESET = 1

RATE = 0

AO1

IN

4 TO 20 mA

OUTPUT TYPE = CAT

IN LOW LIMIT = 0

IN HIGH LIMIT = 100

OUT LOW LIMIT = 4

OUT HIGH LIMIT = 20

FB

AO1 BC

SP2

SP1

SP1 OV

Figure 3-24 Function Block Diagram Of Set Point Profile Control Of Figure 3-16

Figure 3-24 basically depicts all the components of the Figure 3-16’s control configuration with a set
point profiler function block denoted by SP1. The profiler’s output (SP1 OV) is connected to the remote
set point input of LP1. Depending on the model number of the instrument, up to four set point profiler
function blocks (SP1 through SP4) may be included within the instrument’s feature capacities. Note that
while the profiler of SP1 was specified in Figure 3-24’s diagram, any of the profilers within the instrument
could have been used.

When a set point profile is executed, discrete inputs are typically used in conjunction with external
switches to control the set point profiler function block. For example, the set point profiler function block
can be programmed to start, hold, or reset based on discrete input statuses. See Figure 3-25.

External

Switches

DI1

DI1 OS

DI2

DI2 OS

DI3

DI3 OS

AI1

TYPE J

THERMOCOUPLE

AI1 OV

INPUT TYPE = J

RANGE LOW = 0

RANGE HIGH = 1000

LP1

PV

LP1 OV

TYPE = STANDARD

SP1 = 500

SP2 = SP1 OV

GAIN = 10

RESET = 1

RATE = 0

AO1

IN

4 TO 20 mA

OUTPUT TYPE = CAT

IN LOW LIMIT = 0

IN HIGH LIMIT = 100

OUT LOW LIMIT = 4

OUT HIGH LIMIT = 20

FB

AO1 BC

SP2

SP1

SP1 OV

START

HOLD

RESET

“OS” = OUTPUT STATE

Figure 3-25 Discrete Inputs Controlling Execution Of Set Point Profiler Function Block