Step 9. wiring the fireplace, Step 8. gas pressure requirements – Heat & Glo Fireplace ST-38GTV User Manual

Page 14

Advertising
background image

14

!

Step 9. Wiring the Fireplace

NOTE: Electrical wiring must be installed by a licensed

electrician.
CAUTION: DISCONNECT REMOTE CONTROLS IF YOU

ARE ABSENT FOR EXTENDED TIME PERIODS. THIS

WILL PREVENT ACCIDENTAL FIREPLACE OPERATION.
For Standing Pilot Ignition Wiring
Appliance Requirements
This appliance DOES NOT require 110-120 VAC to operate.

For Direct Spark Ignition (DSI) Wiring
Appliance Requirements

This appliance requires that 110-120 VAC be wired to the

factory installed junction box. Maintain correct polarity when

wiring the junction box.
Optional Accessories

Optional remote control kits require that 110-120 VAC be

wired to the fireplace junction box.
Wall Switch

Position the wall switch in the desired position on a wall. Run

a maximum of 25 feet (7.8m) or less of 16 A.W.G. minimum

wire and connect it to the fireplace ON/OFF switch pigtails.
CAUTION: LABEL ALL WIRES PRIOR TO DISCONNEC-

TION WHEN SERVICING CONTROLS. WIRING ERRORS

CAN CAUSE IMPROPER AND DANGEROUS OPERA-

TION. VERIFY PROPER OPERATION AFTER SERVICING.

WHITE T2

BLACK S1

THERMOPILE

GAS VALVE

RED T1

3\16" PIGGYBACK

CONNECTOR

TH

TH

SWITCH

ON/OFF

THERMOSTAT OR REMOTE

OPTIONAL WALL SWITCH,

LIMIT SWITCH

OFF

ON

BLACK S2

HI-TEMP

GROUND

BLACK L1

BLACK L2

PIGTAIL

REMOTE SWITCH

TP

TP

Figure 10. Standing Pilot Ignition Wiring Diagram

Wall Switch

Position the wall switch in the desired position on a wall.

Run a maximum of 25 feet (7.8 m) or less length of 18

A.W.G. minimum wire and connect it to the fireplace ON/

OFF switch pigtails.
CAUTION: LABEL ALL WIRES PRIOR TO DISCONNEC-

TION WHEN SERVICING CONTROLS. WIRING ERRORS

CAN CAUSE IMPROPER AND DANGEROUS OPERA-

TION. VERIFY PROPER OPERATION AFTER SERVICING.

WARNING: DO NOT CONNECT 110-120 VAC TO

THE GAS CONTROL VALVE OR WALL SWITCH

OR THE APPLIANCE WILL MALFUNCTION

AND THE VALVE WILL BE DESTROYED.

Optional Accessories
Optional fan and remote control kits require that 110-120

VAC be wired to the factory installed junction box before

the fireplace is permanently installed.

Step 8. Gas Pressure Requirements

Pressure requirements for Heat-N-Glo gas fireplaces

are shown in the table below.

Pressure

Natural Gas

Propane

Minimum

5.0 inches

11.0 inches

Inlet Pressure

w.c.

w.c.

Maximum Inlet

14.0 inches

14.0 inches

Gas Pressure

w.c.

w.c.

Manifold

3.5 inches

10.0 inches

Pressure

w.c.

w.c.

A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is

provided on the inlet and outlet side of the gas control for a

test gauge connection to measure the manifold pressure.
The fireplace and its individual shut-off valve must be

disconnected from the gas supply piping system during

any pressure testing of the system at test pressures in

excess of one-half (1/2) psig (3.5 kPa).
The fireplace must be isolated from the gas supply piping

system by closing its individual shut-off valve during any

pressure testing of the gas supply piping system at test

pressures equal to or less than one-half (1/2) psig (3.5 kPa).