CAUTION: IF JOINTS BETWEEN THE FINISHED WALLS

AND THE FIREPLACE SURROUND (TOP AND SIDES)

ARE SEALED, A 300°

F. MINIMUM SEALANT MATE-

RIAL MUST BE USED. THESE JOINTS ARE NOT RE-

QUIRED TO BE SEALED. ONLY NON-COMBUSTIBLE

MATERIAL (USING 300° F. MINIMUM ADHESIVE, IF

NEEDED) CAN BE APPLIED AS FACING TO THE FIRE-

PLACE SURROUND. SEE THE DIAGRAM BELOW.

Hearth Extensions

A hearth extension may be desirable for aesthetic reasons.

However, ANSI or CAN/CGA testing standards do not require

hearth extensions for gas fireplace appliances.

Installing the Trim

Combustible materials may be brought up to the specified

clearances on the side and top front edges of the fireplace,

but MUST NEVER overlap onto the front face. The joints

between the finished wall and the fireplace top and sides

can only be sealed with a 300° F. (149° C) minimum sealant.
Install optional marble and brass trim surround kits as

desired. Marble, brass, brick, tile, or other non-combustible

materials can be used to cover up the gap between the

sheetrock and the fireplace.
Do not obstruct or modify the air inlet/outlet grilles. When

overlapping on both sides, leave enough space so that the

controls can be accessed and the trim door and glass door

can be removed.

Step 11. Installing Trim, Logs & Ember Material

Figure 14.

Sealant Material

Placing the Ember Material
Two separate bags of ember material are shipped with this

gas fireplace:
• The bag labeled Golden Ember (GE-93) is flame colo-

rant material.

• The bag labeled Glowing Ember (050-721) is standard

glowing ember material.

To place the ember material:
• Lift the trim door up and out from the unit.
• Remove the wing nuts and screws around the glass door.

Figure 15. Glass Assembly

STUD

HEADER

FINISHED

WALL

SEAL JOINT

(300° F/149° C MIN.)

GLASS

ASSEMBLY

MOUNTING

STUD

GLASS CLIP

WING NUT

Positioning the Logs
If the gas logs have been factory installed they should not

need to be positioned.
If the logs have been packaged separately, refer to the

installation instructions that accompany the logs. Save the

log instructions with this manual.
If sooting occurs, the logs might need to be repositioned

slightly to avoid excessive flame impingement.

Step 10. Finishing

Figure 13 shows the minimum vertical and corresponding

maximum horizontal dimensions of fireplace mantels or other

combustible projections above the top front edge of the

fireplace. See Figures 2 and 3 for other fireplace clearances.
Only non-combustible materials may be used to cover the

black fireplace front.

WARNING: WHEN FINISHING THE FIREPLACE,

NEVER OBSTRUCT OR MODIFY THE AIR IN-

LET/OUTLET GRILLES IN ANY MANNER.

Figure 13.

Minimum Vertical and Maximum Horizontal

Dimensions of Combustibles above Fireplace

!

12"

MINIMUM

8" MAXIMUM

MANTLE

HOOD

31”

CEILING