4300 Wood Stove Series (ACC)

Hearth & Home Technologies welcomes you to our tradi-

tion of excellence! In choosing a Quadra-Fire appliance,

you have our assurance of commitment to quality, durabil-

ity, and performance.
This commitment begins with our research of the market,

including ‘Voice of the Customer’ contacts, ensuring we

make products that will satisfy your needs. Our Research

and Development facility then employs the world’s most

advanced technology to achieve the optimum operation of

our stoves, inserts and fireplaces. And yet we are old-fash-

ioned when it comes to craftsmanship. Each unit is meticu-

lously fabricated and surfaces are hand-finished for lasting

beauty and enjoyment. Our pledge to quality is completed

as each model undergoes a quality control inspection.
We wish you and your family many years of enjoyment in

the warmth and comfort of your hearth appliance. Thank

you for choosing Quadra-Fire.

and Welcome to the Quadra-Fire Family

!

Serial No.

Model Name

Test Lab &

Report No.

Mfg. Date

SAMPLE OF SERIAL NUMBER / SAFETY LABEL

LOCATION: BACK OF APPLIANCE

INSTALLATION: FULL VERTICAL OR HORIZONTAL WITH MINIMUM 2 FOOT VERTICAL OFF STOVE TOP

INSTALLATION: ENTIÈREMENT VERTICALE OU HORIZONTALE AVEC 609mm VERTICAL MINIMUM DU HAUT DU POÊLE

SINGLE WALL PIPE

A

B

C

D

E

F

G

H

Flat Top Model

18 (457) 15.5 (394) 26 (660) 17 (432) 10 (255) 18.5 (470) 52.5 (1334) 18 (457)*

Step Top Model

12 (305) 8.5 (216) 23 (584) 13 (330) 2 (51) 13 (330)

50.5 (1283) 18 (457)*

DOUBLE WALL PIPE

Flat Top Model

13 (330) 10.5 (267) 24.5 (622) 15 (381) 10 (255) 18.5 (470) 52.5 (1334) 10 (254)

Step Top Model

10 (254) 6.5 (165) 23 (584) 13 (330) 2 (51) 13 (330)

50.5 (1283) 5 (127)

INSTALLATION: 90o ELBOW OFF TOP OF STOVE THROUGH BACKWALL

INSTALLATION: 90o DU COURBURE AU DESSUS DE HAUT DU POÊLE A TRAVERS LE MUR ARRIÈRE

DOUBLE WALL PIPE

Flat Top Model

8.5 (216) 6 (152) 24.5 (622) 15 (381) 10 (254) 18.5 (470) 52.5 (1334) 18 (457)*

Step Top Model

7.5 (191) 4 (102) 19 (483) 9 (229) 2 (51) 13 (330)

50.5 (1283) 18 (457)*

INSTALLATION: ALCOVE -

Six inch (6 inches) (152mm) diameter listed DOUBLE WALL air insulated connector pipe with UL103 HT* listed factory-built Class "A" chimney, or a masonry chimney. (Mobile Home

must be equipped with a spark arrestor.) Maximum depth of Alcove shall be no more than 48 inches (1220mm) with a minimum height of 45.5 inches (1156mm) to top of unit, and the referenced clearances. Please

refer to the clearances below for minimum Alcove height requirement to top of unit.

INSTALLATION: ALCÔVE - De six (6 inches) (152mm) de diamètre, le connecteur du conduit d'air isolé pour mur double avec une cheminée bâtit en usine UL103HT de Classe "A", ou une cheminée de briques. (Les maisons

mobiles doivent être équipées d'un arrêt d'étincelle). La profondeur maximum de l'alcôve ne doit pas être de plus de 48 inches (1220mm) avec une hauteur minimum de 45.5 inches (1156mm) du haut de l'appareil, et des espaces

libres alloués. Référez vous s'il vous plaît aux dégagements repirs ci-dessus pour la hauteru minimum requise entre le dessus ole l'appareil et l'alcove (de la chimineé).

DOUBLE WALL PIPE

Flat Top Model

13 (330) 10.5 (267) 24.5 (622) 15 (381)

N/A

N/A

52.5 (1334)

N/A

Step Top Model

10 (254) 6.5 (165) 23 (584) 13 (330)

N/A

N/A

37 (940)

N/A

*In Canada must comply with Standard CAN/ULC-S629-M87 for the 650oC Factory-built chimney.

*Au Canada doit conformer a CAN/ULC-S629-M87 la norme pour 650oC cheminée bâtit en usine.

*

NFPA 211 MINIMUM CLEARANCES - NOT TESTED

SPÉCIFICATIONS DE LA VENTILATION:

MUR SIMPLE: De six (6 inches) (152mm) de diamètre le connecteur de conduit de minimum

d'acier noir ou bleu de minimum de 24MSG, avec une cheminée bâtit en usine UL103HT* de

Classe "A", adéquate pour usage avec les combustions solides, ou une cheminée de briques,

avec espaces libres référés.

MUR DOUBLE: De six (6 inches) (152mm) de diamètre, le connecteur du conduit d'air isolé

pour mur double avec une cheminée bâtit en usine UL103HT* de Classe "A:, ou une cheminée

de briques, avec espaces libres alloués.

MAISON MOBILE: Utiliser un conduit de mur double par Dura-Vent DVL, Selkirk Metalbestos

DS ou Security DL. Doit être équipé d'un arrêt d'étincelle. Utiliser les espaces libres pour mur

double comme mentionné ci-bas.

MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS: In Inches & (Millimeters)

NOTE: All "A" , "C" and "F" Dimensions are to inside diameter of the flue collar.

LISTED ROOM HEATER, SOLID FUEL TYPE.

ALSO FOR USE IN MOBILE HOMES. (UM) 84 HUD

1445 N. Highway, Colville, WA 99114

www.quadrafire.com

I

nstall and use only in accordance with

manufacturer's installation and operating

instructions. Contact local building or fire

officials about restrictions and installation

inspections in your area. Do not obstruct the

space beneath heater.

WARNING - For Mobile Homes: Do not install

in a sleeping room. An outside combustion air

inlet must be provided and unrestricted while unit

is in use. The structural integrity of the mobile

home floor, ceiling and walls must be maintained.

The stove needs to be properly grounded to the

frame of the mobile home. Components required

for mobile home installation: Outside Air Kit, Part

Number OAK-ACC.

Refer to manufacturer's instructions and

local codes for precautions required for passing

chimney through a combustible wall or ceiling

and maximum offsets.

Inspect and clean chimney frequently - Under

Certain Conditions of Use, Creosote Buildup May

Occur Rapidly.

Do not connect this unit to a chimney serving another

appliance.

Optional Components: Optional Blower, Part

BK-ACC.

Electrical Rating: 115 VAC, 1.2 Amps, 60 Hz.

Route power cord away from unit. Do not route

cord under or in front of appliance.

DANGER: Risk of electrical shock.

Disconnect power supply before servicing.

Replace glass only with 5mm ceramic available

from your dealer.

Do not use grate or elevate fire. Build wood fire

directly on hearth.

Do not overfire - if heater or chimney

connector glows, you are overfiring.

Operate only with the fuel loading door

closed. Open only to add fuel to the fire.

CAUTION

:

U.S. ENVIRONMENTAL PROTECTION AGENCY - Certified to

comply with July 1990 particulate emission standards.

2008 2009 2010 Jan. Feb. Mar. Apr. May June July Aug. Sept. Oct. Nov. Dec.

PREVENT HOUSE FIRES

FLOOR PROTECTION

:

Floor protector must be a 3/8 inch min. thickness,

non-combustible material or equivalent, extending

beneath heater and to front/sides/rear as indicated on

the diagram below. Exception: Non-combustible floor

protections must extend beneath the flue pipe when

installed with horizontal venting and extend 2 inches

(51mm) beyond each side.

O-T L

Tested and

Listed by

Portland

Oregon USA

OMNI-Test Laboratories, Inc.

C

Report / Rapport

#061-S-67-7

TESTED TO:/ TESTÉ À:

UL 1482, ULC S627-00

HOT WHILE IN OPERATION DO NOT TOUCH, KEEP CHILDREN AND CLOTHING AWAY. CONTACT MAY CAUSE SKIN BURNS. KEEP FURNISHINGS AND OTHER

COMBUSTIBLE MATERIAL FAR AWAY FROM THE APPLIANCE. SEE NAMEPLATE AND INSTRUCTIONS.

VENT SPECIFICATIONS:

SINGLE WALL: Six inch (6 inches) (152mm) diameter, minimum 24 MSG black or blued steel connector

pipe, with a listed factory-built UL103HT* Class "A" chimney, suitable for use with solid fuels, or a

masonry chimney, and the referenced clearances.

DOUBLE WALL: Six inch (6 inches) (152mm) diameter, listed double wall air insulated connector pipe

with listed factory-built UL103HT* Class "A" chimney, or a masonry chimney and the referenced

clearances

MOBILE HOME: Use double wall pipe by Dura-Vent DVL, Selkirk Metalbestos DS or Security DL double

wall connector pipe. Must be equipped with a spark arrestor. Apply double wall clearances below when

installing unit.

SERIAL NO. / NUMÉRO D

E

SÉRIE

4300 ACC Series

R

7037-136

CHAUD LORS DE L'OPÉRATION. NE PAS TOUCHER. GARDEZ LES ENFANTS ET LES VÊTEMENTS LOIN DE L'ESPACE DÉSIGNÉ DE L'INSTALLATION. LE CONTACT PEUT CAUSER DES

BRÛLURES À LA PEAU. GARDEZ LES MEUBLES ET LES MATÉRIAUX COMBUSTIBLES LOIN DE L'ESPACE DÉSIGNÉ DE L'APPAREIL. VOIR L'ÉTIQUETTE ET LES INSTRUCTIONS.

ATTENTION:

APPAREIL DE CHAUFFAGE DE PIÈCE, DE TYPE DE

COMBUSTIBLE SOLIDE, POUR USAGE DANS LES

MAISONS MOBILES. (UM) 84 HUD. "Pour Usage

Avec Bois Solide Seulement"

Installez et utilisez en accord avec les instructions

d'installation et d'opération du fabricant. Contactez le

bureau de la construction ou le bureau des incendies au

sujet des restrictions et des inspections d'installation dans

votre voisinage. Ne pas obstruez l'espace en dessous de

l'appareil.

AVIS - Pour Les Maisons Mobiles: Ne pas installer dans

une chambre à coucher. Un tuyau extérieur de combustion

d'air doit être installé et ne doit pas être obstrué lorsque

l'appareil est en usage. La structure intégrale du plancher,

du plafond et des murs de la maison mobile doit être

maintenue intacte. L'appareil de chauffage doit être fixé à

la charpente de la maison mobile. Les composants requis

pour l'installation des maisons mobiles: Assemblage d'air

extérieur, Numéro de Pièce OAK-ACC..

Référez vous aux instructions du fabricant et des codes

locaux pour les précautions requises pour passer une

cheminée à travers un mur ou un plafond combustibles, et les

compensations maximums.

Inspectez et nettoyez la cheminée fréquemment. Sous

certaines conditions, il se peut que la créosote s'accumule

rapidement.

Ne pas connecter cet appareil à une cheminée servant un

autre appareil.

Composants Optionnels: Ventilateur Optionnel, Pièce

BK-ACC.

Puissance Électrique: 115 VAC, 1.2 Amps, 60 Hz.

Éloignez le fil électrique de l'appareil. Ne pas faire passer

le fil électrique au dessus ou en dessous de l'appareil.

DANGER: Il y a risque de décharge électrique.

Déconnectez le fil électrique de la prise de contact avant le

service.

Remplacez la vitre seulement avec une vitre céramique de

5 mm disponible chez votre fournisseur.

N'élevez pas le feu. Bâtissez le feu de bois directement sur

l'âtre.

Ne pas surchauffer. Si l'appareil de chauffage ou le tuyau

de cheminée rougissent, vous surchauffez.

Opérez l'appareil seulement lorsque la porte de

chargement est fermée. Ouvrez la porte seulement lorsque

vous devez ajouter des combustibles dans le feu.

PRÉVENTION DES FEUX DE MAISON

PROTECTION DU PLANCHER:

Le protecteur de plancher doit être d'un minimum de 3/8

inch d'épaisseur, de matériel incombustible ou équivalent,

s'étendant du dessous de l'appareil de chauffage à

l'avant, aux cotés et à l'arrière comme indiqué sur le

diagramme suivant. Exception: Les protections

incombustibles du plancher doivent s'étendre en dessous

du conduit de cheminée lorsqu'installées avec une

ventilation à l'horizontale et s'étendre de 2 inches (51mm)

de chaque côté.

ESPACES LIBRES MINIMUM DES MATÉRIAUX COMBUSTIBLES:En Pouces & (millimètres)

NOTE: Toutes les dimensions "A", "C", et "F" sont à partir du diamètre intérieur de l'entrée du conduit.

BACKWALL/SIDEWALL

MUR ARRIÈRE/MUR DE CÔTÉ

CORNER INSTALLATION

/

INSTALLATION DU COIN

ALCOVE TOP VIEW /

VUE DU HAUT DE L'ALCÔVE

ALCOVE SIDE VIEW /

VUE DE CÔTÉ DE L'ALCÔVE

DO NOT REMOVE THIS LABEL / NE PAS ENLEVER L'ÉTIQUETTE

Made in U.S.A./Fait Aux États-Unis

Manufactured by:

Fabriqué par:

G

A

B

C

D

A

B

C

D

90

o

OFF TOP

UP & OUT CEILING CLEARANCE

ESPACE LIBRE DU DESSUS DE

L'APPAREIL AU PLAFOND AVEC 90

DE COURBURE

STOVE TO CEILING CLEARANCE
ESPACE LIBRE DU POÊLE AU

PLAFOND

G

G

H*

E

F

E

F

G

H

G

A

B

16" from glass

8"

USA

Fuel loading door

4-1/2"

3-1/2"

31-5/8" minimum

40-7/16"

minimum

CANADA

203mm (8")

203mm

(8")

203mm

(8")

457mm (18")

1281mm

(50-7/16")

minimum

1080mm (42-1/2")

minimum

CONDUIT DU MUR SIMPLE

Modèle au dessus en appartement

Modèle au dessus en escalier

CONDUIT DU MUR DOUBLE

Modèle au dessus en appartement

Modèle au dessus en escalier

CONDUIT DU MUR DOUBLE

Modèle au dessus en appartement

Modèle au dessus en escalier

CONDUIT DU MUR DOUBLE

Modèle au dessus en escalier

Modèle au dessus en appartement

007003

SAMPLE

Advertising
This manual is related to the following products: