Features

Advanced Menu Options

5. SPAN 2 : Unless you have a multi-stage conventional or heat pump system, there

is no need to change the second stage span. If you do, use the or buttons to

adjust between 1, 2, or, 3. Press

Next

once this has been changed or if you need

to make no changes. Second stage span acts the same as your primary, but it

determines when and how long your second stage heat runs.

6. Auto Season Span: When your thermostat is set to “Auto”, this setting allows the

thermostat to switch between heat and cool modes based off the room temperature.

The auto season span limits how close your heat and cool set temperatures can be

to allow the thermostat to switch between the two modes properly. Use the or

buttons to adjust between 3

O

to 6

O

. Press

Next

to advance to the next option.

Example: If you set your heat temperature for a schedule to be 68

O

, the lowest you

would be able to set your cool temperature for that schedule would be 73

O

, with an

auto season span of 5. Assuming you have a stage 1 span of 2, see page 40 for stage

1 span description, a heating temperature of 68

O

, and a cooling temperature of 73

O

,

your thermostat will activate heat at 67

O

and run till 69

O

and shut off. If the temperature

continues to rise up to 74

O

, 1

O

above your cooling temperature, your thermostat will

switch to cooling, run to 72

O

and then shut down. The thermostat will switch back to

heating if the temperature drops to 67

O

, 1

O

below your heat temperature.

7. Temperature Calibration: If your thermostat seems to be running a degree or two

hot or cold, you can set the calibration here. Use the or buttons to adjust

between -2

O

to 2

O

. Press

Next

to advance to the next option.