7 programming – Honeywell ELECTRONIC REFRIGERATION CONTROL PCR-300 User Manual
Page 13
6.7 Manual defrosting
Press and hold down the
key for 5 seconds.
The manual defrosting process will be initiated.
7 Programming
Access to the second programming level:
¼ Press and hold down the
,
and
keys at the same time for
approx. 5 seconds
(Display: E01 for PCR-300, E00 for PCR-300RC).
¼ Use
or
key to select parameters.
¼ Setting: Press and hold down the
key. Adjust the setpoint value
to the desired figure using the
or
key.
¼ Do not display altered parameter data before saving the data, as it
would be reversed to its original value in the process.
7.1 Input parameters and input ranges
Parameter in Display
Setting range
Preset
(
or
)
(
and
or
)
E00
Time, only for PCR-300RC
00.0 to 23.5 hours
12’0 hours
E01
Cold store temp. difference
1 to 20 K
2 K
E02
Time between 2 defrost cycles
1 to 24 hours
8 h
☛ Once the controller has been switched on, defrosting occurs
for the first time at the end of the first time interval.
☛ After defrosting has been initiated manually, the next time
defrosting takes place is after a complete time interval has
elapsed.
☛ If the time interval between two defrost cycles is changed
when the system is in operation, the new time interval will
not be applied until after the next time defrosting has
occurred.
For PCR-300RC only:
E2’1 1st defrost time
––– (none), 00.1 to 23.5 hours
––– (none)
E2’2 2st defrost time
––– (none), 00.1 to 23.5 hours
01’0 hours
E2’3 3st defrost time
––– (none), 00.1 to 23.5 hours
07’0 hours
E2’4 4st defrost time
––– (none), 00.1 to 23.5 hours
13’0 hours
E2’5 5st defrost time
––– (none), 00.1 to 23.5 hours
19’0 hours
E2’6 6st defrost time
––– (none), 00.1 to 23.5 hours
––– (none)
13