6.7 Manual defrosting

Press and hold down the

key for 5 seconds.

The manual defrosting process will be initiated.

7 Programming

Access to the second programming level:
¼ Press and hold down the

,

and

keys at the same time for

approx. 5 seconds
(Display: E01 for PCR-300, E00 for PCR-300RC).

¼ Use

or

key to select parameters.

¼ Setting: Press and hold down the

key. Adjust the setpoint value

to the desired figure using the

or

key.

¼ Do not display altered parameter data before saving the data, as it

would be reversed to its original value in the process.

7.1 Input parameters and input ranges

Parameter in Display

Setting range

Preset

(

or

)

(

and

or

)

E00

Time, only for PCR-300RC

00.0 to 23.5 hours

12’0 hours

E01

Cold store temp. difference

1 to 20 K

2 K

E02

Time between 2 defrost cycles

1 to 24 hours

8 h

Once the controller has been switched on, defrosting occurs

for the first time at the end of the first time interval.

After defrosting has been initiated manually, the next time

defrosting takes place is after a complete time interval has
elapsed.

If the time interval between two defrost cycles is changed

when the system is in operation, the new time interval will
not be applied until after the next time defrosting has
occurred.

For PCR-300RC only:

E2’1 1st defrost time

––– (none), 00.1 to 23.5 hours

––– (none)

E2’2 2st defrost time

––– (none), 00.1 to 23.5 hours

01’0 hours

E2’3 3st defrost time

––– (none), 00.1 to 23.5 hours

07’0 hours

E2’4 4st defrost time

––– (none), 00.1 to 23.5 hours

13’0 hours

E2’5 5st defrost time

––– (none), 00.1 to 23.5 hours

19’0 hours

E2’6 6st defrost time

––– (none), 00.1 to 23.5 hours

––– (none)