Clearing alarm:
Press the
key.
All alarm messages, with the exception of AL2, are also reset by
switching off the operating voltage. AL2 can only be reset using
the
key.
10 Problem solving
Fault
Cause
Remedy
Evaporator fan does not
Evaporator
Refit
switch on during
sensor T2 has
sensor.
cooling when the
fallen out of
programmed setting
the fins.
of parameter E11
is set to position 3
(fan run-on).
For PCR-300RC only:
Back-up battery
Switch on
The real-time clock
is switched off.
back-up
stops or indicates the
battery
wrong time in the event
see
of a power failure.
Section 5.3.