B. Mantel and Wall Projections

WARNING! Risk of Fire! Comply with all minimum clear-
ances to combustibles as specifi ed. Framing or fi nishing
material closer than the minimums listed must be construct-
ed entirely of noncombustible materials (i.e., steel studs,
concrete board, etc).

Clearance to combustible material under the insert is 1/4
inch (6 mm). Clearance from top of fi replace opening for
combustibles extending 12 inches max. is 12 inches.

• Use leveling legs to raise insert minimum 1/4 inch (6 mm)

above combustible material or outer wrap of factory built
fi rebox.

Combustible facings must not extend behind the insert
surround. For non-combustible material specifi cations
refer to section 1.E.

EXISTING NON-COMBUSTIBLE FACING

12 IN.
MAX.

12 IN. MIN.

2 IN.
MAX.

10 IN. MIN.

Figure 5.3 Mantel Clearance