Hoshizaki F043-809 KMD-410MWH User Manual
Page 19
 
15
S2 Dip Switch Setting
No. 6
Anti-Slush Control
OFF
Activated (Ver. 1.0)
ON Deactivated
 
 
Control Board P01771-02
k) Harvest Promotion Control (S2 dip switch 2) [Program Ver. 3.1, Ver. 3.2]
Do not adjust. This must be left in the factory default position or the unit will not operate 
properly. 
It is deactivated on the KMD-410 series. 
When activated, this control promotes harvest of ice on the evaporator that is hard to 
remove. If the harvest cycle exceeds 6 minutes, the pump motor starts to operate for a 
maximum of 3 minutes. 
 
S2 Dip Switch Setting
No. 2
Harvest Promotion
Control
OFF Activated
ON Deactivated
l) Refill Counter (S2 dip switch 3) [Program Ver. 3.1, Ver. 3.2]
Do not adjust. This must be left in the factory default position or the unit will not operate 
properly. The KMD-410MAH and KMD-410MWH refill 1 time. 
m) Harvest Completion Detection Control (S2 dip switch 4) [Program Ver. 3.1, Ver. 3.2]
Do not adjust. This must be left in the factory default position or the unit will not operate 
properly. 
It is deactivated on the KMD-410 series. 
When activated, this control determines whether ice remains on the evaporator at the end of 
a harvest cycle and at the beginning of a freeze cycle. If ice drops and activates the bin 
control switch in the last 10 seconds of a harvest cycle, the control determines that ice still 
remains on the evaporator and extends the harvest cycle for 30 seconds. If the bin control 
switch is activated at the beginning of a freeze cycle, the control determines that ice still 
remains on the evaporator and starts a harvest cycle after the minimum freeze cycle time 
has passed. 
 
S2 Dip Switch Setting
No. 4
Harvest Completion
Detection Control
OFF Deactivated
ON Activated
n) Overfreeze Detection Control (S2 dip switch 5) [Program Ver. 3.1, Ver. 3.2]
Do not adjust. This must be left in the factory default position or the unit will not operate 
properly. 
It is deactivated on the KMD-410 series. 
When activated, the thermistor detects the temperature of the evaporator outlet to find 
overfreeze in a harvest cycle and at the beginning of a freeze cycle. If the difference 
between the maximum temperature after the water saver timer starts counting and the