Step 3. Lay Out Communications and Power

Wiring

L

ON

W

ORKS

Layout

The communications bus, L

ON

W

ORKS

, is a 78-kilobit serial link

that uses transformer isolation and differential Manchester

encoding. Wire the L

ON

W

ORKS

using wires with specifications

set forth in Table 10. An FTT L

ON

W

ORKS

can be wired in

daisy chain, star, loop or any combination thereof as long as

the max. wire length requirements given in Step 2 are met.

NOTE: Due to the transformer isolation, the bus wiring does

not have a polarity; that is, it is not important which

of the two L

ON

W

ORKS

terminals are connected to

each wire of the twisted pair.

L

ON

W

ORKS

networks can be configured in a variety of ways,

but the rules listed in Table 9 always apply. Fig. 13 and Fig.

14 depict two typical daisy chain L

ON

W

ORKS

network layouts;

one as a single bus segment that has 60 nodes or less, and

one showing two segments. Fig. 15 shows examples of free

topology bus layouts. The bus configuration is set up using

the Network Manager tool.

Excel 10 W7752

FCU Controller

Excel 10 W7754

FCU Controller

Excel 5000

Honeywell

D-71101 Schönaich

Made in Germany

12

10 11 12

9

Honeywell

te

rmi

nati

on

module

Fig. 13. L

ON

W

ORKS

wiring layout for one daisy-chain network segment

Excel 10 W7752

FCU Controller

Excel 10 W7754

FCU Controller

Excel 5000

Honeywell

D-71101 Schönaich

Made in Germany

12

10 11 12

9

Honeywell

Excel 10 W7752

FCU Controller

Excel 10 W7754

FCU Controller

Honeywell

D-71101 Schönaich

Made in Germany

12

10 11 12

9

Honeywell

max. 60 nodes

max. 60 nodes

termination

mo

dule

ter

m

ination

module

ter

m

ination

module

LonWorks

router

Fig. 14. L

ON

W

ORKS

wiring layout for two daisy-chain network segments