Excel 10 fcu controller lns plug-ins user guide – Honeywell EXCEL 10 W7752D User Manual

Page 43

Advertising
background image

EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE

41 EN2B-0285GE51

R0909

Table C2. Configuration Variables for Excel 10 FCU Controllers

NV name

field name

engineering units:

English (metric) or states

plus range

digital

state

or

value

default comments

nciFcuConfig DI1_config

BYTE
DI_WINDOW_CLOSED
DI_OCCUPIED_SENSOR
DI_AIR_FLOW
DI_CHANGEOVER_COOL
DI_WINDOW_OPEN
DI_UNOCCUPIED_SENS
DI_NO_AIR_FLOW
DI_CHANGEOVER_HEAT
DI_MOVEMENT
DI_NO_MOVEMENT
DI_NOT_USED


0
1
2
3
4
5
6
7
8
9
255

DI_NOT_USED

This configuration variable specifies the digital input function and type
of switch. The option to be selected is the one which is the condition for
a closed switch contact (e.g., normally-closed window switch contact =
DI_WINDOW_CLOSED, normally-open window switch contact =
DI_WINDOW_OPEN).

DI_MOVEMENT and DI_NO_MOVEMENT are supported starting with
FCU2 version 1.0.3. These configuration settings cause the controller
to retain the occupied state for 15 minutes after the last movement is
detected.




nciFcuConfig fan_config

BYTE
NO_FAN
ONE_SPEED
TWO_SPEED
THREE_SPEED


0
1
2
3

THREE_SPEED

This configuration variable specifies the type of fan connected to the
controller.



nciFcuConfig output_mode[0] BYTE

OUTP_COOLING
OUTP_HEATING
OUTP_CHANGEOVER
OUTP_NOT_USED


0
1
2
255

OUTP_HEATING This

configuration variable specifies the operating mode of the output

1.



nciFcuConfig output_mode[1] BYTE

OUTP_COOLING
OUTP_HEATING
OUTP_CHANGEOVER
OUTP_NOT_USED


0
1
2
255

OUTP_COOLING This

configuration variable specifies the operating mode of the output

2. This setting is ignored for nciNumValve = TWO_PIPE.