Fig. 69. Transformer example

Use quick-acting backup fuse 10 A (or automatic H16 or L16)
to protect transformer primary side. On the primary side of the
CRT 2, there is a fusible output of type M 0.315 A (T) 250 V
for the purpose of fine fusing.

NOTE: When selecting the appropriate transformer, con­

sider the number of Distributed I/O modules (see
worst-case power consumption information below) to
be used as well as the power requirements of all
active sensors and actuators connected to the
transformer.

CRT-Series

Table 12. Overview of CRT Series AC/DC current

Transformer max. AC current

max. DC current

CRT 2

2 A

0.5 A = 500 mA

CRT 6

6 A

1.3 A = 1300 mA

CRT 12

12 A

2.5 A = 2500 mA

Fig. 70. AC/DC current graphs

1450 Series
All transformers of the 1450 series are designed for 50/60 Hz
AC and have insulated accessory outputs. The transformers
include built-in fuses, line transient/surge protection and AC
convenience outlets and meet NEC class 2 requirements.

EXCEL 500/600 INSTALLATION INSTRUCTIONS

Table 13. 1450 Series transformers

Part #

1450 7287

Primary side

Secondary side

-001

120 Vac

24 Vac, 50 VA

-002

120 Vac

2 x 24 Vac, 40 VA and 100 VA
from separate transformer

-003

120 Vac

24 Vac, 100 VA and 24 Vdc
600 mA

-004

240/220 Vac 24 Vac, 50 VA

-005

240/220 Vac

2 x 24 Vac, 40 VA and 100 VA
from separate transformer

-006

240/220 Vac

24 Vac, 100 VA and 24 Vdc
600 mA

Standard Transformers
Standard commercially available transformers must fulfill the
specifications stated in Table 14.

Table 14. Requirements for standard transformers

Output voltage

Impedance

AC current

24.5 Vac to 25.5 Vac ≤ 1.15 ohms

max. 2 A

24.5 Vac to 25.5 Vac ≤ 0.40 ohms

max. 6 A

24.5 Vac to 25.5 Vac ≤ 0.17 ohms

max. 12 A

Screw Terminal Block Installation Procedure

WARNING

High Voltage
Risk of death or electrical shock.
— Do not connect line power supply directly to the

terminals.

— Insulate devices with 120 Vac / 230 Vac by a

transformer.

1. Make sure that the power supply of the cabinet is

disconnected.

2. Make sure that the power supply of the cabinet is

disconnected and the communication module is
plugged in the housing.

IMPORTANT

When installing a separate external transformer, do
not connect the cabinet ground to the controller
system ground.

3. If the distance between the controller and an actuator or

sensor with 24 Vac supply is greater than 550 ft
(170m):

a) Choose a transformer from the transformers

listed in section "Power Supply" on page 32.

b) Connect the chosen transformer directly to the

actuator or sensor.

33