EXCEL 500/600 INSTALLATION INSTRUCTIONS

Inside the cabinet:

J-Y-(ST)Y 2 x 2 x 0.8

Outside the cabinet:

A-Y-(ST) 2 x 2 x 0.8

In principle, data transmitting cables should be shielded in
case of RFI.
The following summarizes cable types and gives selection
guidance. Note that baud rate and maximum bus length are
related to each other.

Table 19. C-Bus cable types

Cable type

Description

Recommended for

J-Y-(ST)Y
2 x 2 x 0.8

shielded,
twisted pair

Europe
Inside cabinet

A-Y-(ST)Y
2 x 2 x 0.8

shielded,
twisted pair

Europe
Outside cabinet

AK 3702

unshielded,
twisted pair

US
not approved for Europe

AK 3740A

shielded

US (low-cost)
not approved for Europe

Belden 9842 twisted pair

Europe
US also possible

Belden 9841 shielded

US

AK 3702

unshielded,
twisted pair

US
not approved for Europe

AK 3740A

shielded

US (low-cost)
not approved for Europe

Each end of the shield on the C-Bus should be connected to
the shield terminal of the respective device. Do not connect it
to the cabinet ground or any other ground points.

C-Bus Extension by Using Repeaters

The C-Bus length can be extended by using repeaters. Each
repeater extends the bus length by 4000 ft (1200 m).
For the US the repeater is available either with or without
housing. In Europe, only the version with housing is allowed.

Table 20. Order no. for repeaters

Description

US order No.

European order no.

without housing

14507324-001

-

with housing

14507324-002

XD509

C-Bus Termination (Excel 600)

The XC6010 CPU module may have either the XD505A or
the XD508 submodules mounted on them for C-Bus
communication. Table 18 provides baud rate information for
selecting the module.

The XD508 submodule is equipped with a DIP switch which
activates (ON position) deactivates (OFF position) a
terminating resistor. Depending on where the controller is
located on the bus the DIP switch settings must be as follows:

Table 21. XD508 DIP switch settings for C-Bus

termination

Controller location

DIP switch setting

beginning or end of bus

ON

middle of bus

OFF

C-Bus Termination (Excel 500)

The XC5010C CPU module contains a switch for setting
different C-Bus baud rates.

Fig. 83. XC5010C C-Bus termination switch location

The bus termination switch for setting the baud rate has three
settings:

Table 22. XC5010 C-Bus termination switch settings

Switch
setting

Baud rate

Notes:

S1

up to 76800 baud
with bus termination

same functionality as
XD508A, up to 76800 baud

S2

up to 76800 baud
without bus
termination

same functionality as
XD508A, up to 76800 baud

S3

up to 9600 baud

same functionality as
XD505A - Default setting

C-Bus Termination (Excel 500-XCL5010)

The communication module for the XCL5010 is equipped with
a DIP switch for the C-Bus to set the bus termination
appropriate for the communication speed.

EN1R-1047GE51 RR0902