EXCEL 500/600 INSTALLATION INSTRUCTIONS

ground

Vi

10 Vdc

Immersion temperature sensor VF 100
Air duct temperature sensor LF 100

25K ohm

Wind sensor:

Wind sensor WS21.

Further connections:

200K ohm

Temperature sensor terminal TF26

Table 15. Accuracy of analog input sensors

Fig. 75. Analog input / low-impedance sensors

Pull-Up Resistor Handling when Using Analog Inputs as
Digital Inputs (O.S. 2.03.xx)

When the input is identified as a DI point in CARE (DI

subtype AI), the internal pull-up resistor is enabled.

10 Vdc

25K ohm

200K ohm

Fig. 76. Analog inputs identified as DI point (O.S. 2.03.xx)

Pull-Up Resistor Handling when Using Analog Inputs as
Digital Inputs (O.S. 2.04.00 or higher)
When the input is identified as a DI point in CARE (DI subtype
AI), the internal pull-up resistor is disabled.

10 Vdc

Range

Measurement error

(without sensor tolerance)

Pt1000

NTC (20k ohms)

-58 to –4 °F (-50 to –20 °C)

1.2 K

5.0 K

-4 to 32 °F (-20 to 0 °C)

0.7 K

1.0 K

32 to 86 °F (0 to 30 °C)

0.5 K

0.3 K

86 to 158 °F (30 to 70 °C)

0.7 K

0.5 K

158 to 212 °F (70 to 100 °C)

1.2 K

1.0 K

212 to 266 °F (100 to 130 °C)

1.2 K

3.0 K

266 to 302 °F (130 to 150 °C)

1.2 K

5.5 K

ground

Vi

ground

Vi

200K ohm

Fig. 77. Analog inputs identified as DI point (O.S. 2.04.00

or higher)

Sensors and Transducers

Passive sensors (NTC 20k ohms)

Room temperature sensor RF20
Inlet temperature sensor VF20A
External temperature sensor AF20

Active sensors (0 to 10 V):

Duct Humidity Sensor H7011A1000
Duct Humidity Sensor H7012A1009

Active sensors (0 (4) to 20 mA):

35