Manufactured (mobile) home installation – haier Gas & Electric Dryer RDE/RDG 350AW User Manual

Page 12

Advertising
background image

English

11

1. Dryer MUST be exhausted outside (outdoors, not beneath the manufactured

home) using metal ducting that will not support combustion. Metal ducting must

be 4 inch (10.16 cm) in diameter with no obstructions. Rigid metal duct

is preferred.

2. If dryer is exhausted through the floor and area beneath the manufactured

home is enclosed, the exhaust system MUST terminate outside the enclosure

with the termination securely fastened to the mobile home structure.

3. When installing a gas dryer into a manufactured home, a provision must be

made for outside make up air. This provision is to be not less than twice the

area of the dryer exhaust outlet.

4. This dryer MUST be fastened to the floor using P/N 0030807899

Manufactured Home Installation Kit. Follow the instructions supplied with

the kit.

5. Refer to previous sections for other important venting requirements.
6. Installation must conform to current Manufactured Home Construction & Safety

Standard (which is a Federal Regulation Title 24 CFR-Part 32-80) or when

such standard is not applicable, with American National Standard for Mobile

Homes. In Canada, the CSA Z240 is applicable.

MANUFACTURED (MOBILE) HOME INSTALLATION