E-bus termination module, W7761a remote i/o device – Honeywell W7761A User Manual

Page 30

Advertising
background image

EXCEL 10 W7761A INPUT/OUTPUT DEVICE

30

74-2699

1

2

3

4

5

6

7

8

E-BUS

24 VAC

W7761A
REMOTE I/O
DEVICE

5

E GND

GND

GND

GND

NOT USED

NOT USED

AI-1 OHM

AI-2 OHM

9

10

11

12

14

J3

15

31

30

29

28

27

26

25

24

23

22

21

20

24 VAC COM

E-BUS

JACK

22 VDC OUT

19

18

17

16

AI-3 OHM

AI-4 OHM

AI-6 V/mA

OUT 7

OUT 6

OUT 5

OUT 4

OUT 8

OUT 1

OUT 3

OUT 2

AI-5 V/mA

13

DI-2

DI-4

DI-1

DI-3

M15278

GND

GND

TRIAC EQUIVALENT CIRCUIT

24 VAC

+

-

24 (H)

24 (N)

24 (H)

24 (N)

INCREASE

DECREASE

MMC325 PNEUMATIC
TRANSDUCER

1

4

3

5

1

2

3

4

EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.
USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM

2

)

WITH A MINIMUM OF 18 AWG (1.O MM

2

), FOR EARTH GROUND WIRE.

REVERSE WIRES (INCREASE/DECREASE) TO REVERSE ACTION
(DIRECT/REVERSE).

MAKE SURE ALL TRANSFORMER/POWER WIRING IS AS SHOWN:
REVERSING TERMINATIONS WILL RESULT IN EQUIPMENT MALFUNCTION.

OPTIONAL 24 VAC WIRING TO NEXT CONTROLLER.

USE 1/4 IN (6 MM) PNEUMATIC TUBING. MINIMUM BRANCH LINE MUST BE
6 FT. (1.8M) OR LONGER.

PNEUMATIC

VALVE

M

B

M

2

Fig. 20. Typical Pneumatic transducer (Series 60 - Floating) to W7761A.

E-Bus Termination Module

One E-Bus Termination Module, part number 209541B is required for a single terminated E-Bus or two E-Bus Termination
Module, part number 209541B for a double terminated E-Bus (see Fig. 21). Refer to the E-Bus Wiring Guidelines form, 74-
2865 for termination module placement rules.