Honeywell W7761A User Manual

Page 47

Advertising
background image

EXCEL 10 W7761A INPUT/OUTPUT DEVICE

47

74-2699

Table C1. Input/Output Points (Left Continued).

Engineering Units:

English (Metric) or

Digital

State

or

Value

of

User Address

NvName

Field Name

States plus Range

State

Default

DestOut1Cmd

nviRemoteCmd(0)

percent
-163 to 163

0

DestOut2Cmd

nviRemoteCmd(1)

percent -163 to 163

0

DestOut3Cmd

nviRemoteCmd(2)

percent -163 to 163

0

DestOut4Cmd

nviRemoteCmd(3)

percent -163 to 163

0

DestOut5Cmd

nviRemoteCmd(4)

percent -163 to 163

0

DestOut6Cmd

nviRemoteCmd(5)

percent -163 to 163

0

DestOut7Cmd

nviRemoteCmd(6)

percent -163 to 163

0

DestOut8Cmd

nviRemoteCmd(7)

percent -163 to 163

0

DI1Sel1Type

ncirioIoSelect

DigitalIn0S1

Active_Short
Active_Open
Unused_DigInput

0
1
255

Unused_DigInput

DI2Sel1Type

ncirioIoSelect

DigitalIn1S1

See DI1Sel1Type Eng.
Units/States column for
selections.

Unused_DigInput

(continued)