EXCEL 10 W7761A INPUT/OUTPUT DEVICE

53

74-2699

Table C1. Input/Output Points (Left Continued).

Engineering Units:

English (Metric) or

Digital

State

or

Value

of

User Address

NvName

Field Name

States plus Range

State

Default

SrcDigIn2Sts

nvoRemoteDigIn(1)

DI2Value

0 to 255

0

nvoRemoteDigIn(1)

DI2State

Refer to the DI1State enumerated list
shown in the Eng. Units/States column.

ST_NUL

SrcDigIn3Sts

nvoRemoteDigIn(2)

DI3Value

0 to 255

0

nvoRemoteDigIn(2)

DI3State

Refer to the DI1State enumerated list
shown in the Eng. Units/States column.

ST_NUL

SrcDigIn4Sts

nvoRemoteDigIn(3)

DI4Value

0 to 255

0

nvoRemoteDigIn(3)

DI4State

Refer to the DI1State enumerated list
shown in the Eng. Units/States column.

ST_NUL

SrcHumidAI5

nvoRemoteHum(0)

percent
-163 to 163

0

SrcHumidAI6

nvoRemoteHum(1)

percent
-163 to 163

0

SrcPressAI5

nvoRemotePres(0)

inw -131.5 to 131.5
kPa (-32.768 to 32.767)

0

SrcPressAI6

nvoRemotePres(1)

inw -131.5 to 131.5
kPa (-32.768 to 32.767)

0

SrcTempAI1

nvoRemoteTemp(0)

degrees F -40 to 240
degrees C (-40 to 116)

0

SrcTempAI2

nvoRemoteTemp(1)

degrees F -40 to 240
degrees C (-40 to 116)

0

SrcTempAI3

nvoRemoteTemp(2)

degrees F -40 to 240
degrees C (-40 to 116)

0

SrcTempAI4

nvoRemoteTemp(3)

degrees F -40 to 240
degrees C (-40 to 116)

0

SrcVoltageAI

nvoRemoteVolt

Volts
0.0 to 10.5

0

)