Heat & Glo • 6000GCF-IPI, 6000GCF-IPILP • 2110-900 Rev. H • 11/08

20

D. Mantel and Wall Projections

WARNING! Risk of Fire! Comply with all minimum clear-
ances as specifi ed. Framing or fi nishing material closer than
the minimums listed must be constructed entirely of noncom-
bustible materials (i.e., steel studs, concrete board, etc).

Figure 5.3 Minimum Vertical and Maximum Horizontal

Dimensions of Combustibles

Note: All
measurements
in inches.

Figure 5.4 Combustible Mantel Leg or Wall Projections

(Acceptable on both sides of opening)

Combustible Mantels

Combustible Mantel Legs or Wall Projections

18

14-1/4

10-1/2

6-3/4

3

7-1/4

8-3/8

9-1/2

10-1/8

11-1/4

MEASUREMENTS FROM TOP EDGE

OF HOOD OR TOP OF UNIT OPENING

1 in.
MIN.

3-1/2 in.

MIN.

3 ft.
MAX.

TOP VIEW

Note: Clearance from fi replace
opening to perpendicular wall.