Install to Fit Your Application

TrueDry DR65 Dehumidification System 69-2089EFS—11

5

Flex duct is recommended in connecting to the TrueDRY DR65 collars to reduce vibration noise.

M24745

electrical requirements:

115 VAC outlet. Ground fault
interrupter (GFI) recommended.

duct sizing: Use minimum 8-in. diameter round for
duct lengths up to 25 ft. Minimum 10-in. required for
lengths longer than 25 ft. Duct branches from the
main inlet/exhaust should be minimum 8-in. round for
2-3 branches, and 8-in. round or larger for 4 branches
or more.
Isolated Areas: Effective dehumidification may
require ducting to isolated or stagnant air flow areas.

SUPPLY

RETURN

AIR HANDLER

TrueDRY

M27325

A

Main Return to Main Return

Ideal when…
• Running TrueDRY DR65 with A/C

operation.

• Minimizing discharge air temperature

(DAT) increase is preferred.

• Space dictates.

SUPPLY

RETURN

AIR HANDLER

TrueDRY

M27324

BACKDRAFT

DAMPER

B

Main Return to Main Supply

Ideal when…
• Running TrueDRY DR65 opposite A/C

operation. Running with A/C operation

requires damper on the exhaust port

to minimize backdraft when TrueDRY

DR65 is not on but A/C is.

• Space dictates.