Transmitter device type holding registers – Honeywell ISM BAND XYR 5000 LINE User Manual
Page 39
 
00005 + (RF ID * 10)
Primary Sensor Value
00006 + (RF ID * 10)
Primary Sensor Value
32-Bit IEEE 
Floating Point 
00007 + (RF ID * 10)
Secondary Sensor Value
00008 + (RF ID * 10)
Secondary Sensor Value
32-Bit IEEE 
Floating Point 
00009 + (RF ID * 10)
Tertiary Sensor Value
00010 + (RF ID * 10)
Tertiary Sensor Value
32-Bit IEEE 
Floating Point 
Note If you have purchased any Wireless Differential Pressure Transmitters, please 
see the User Guide for specific Modbus holding register differences from those listed in 
the following sections. 
6.5.3 Transmitter Device Type Holding Registers
The following are possible values for the Device Type holding registers. Note that the 
register is a 32-bit floating point value for Transmitters. 
Value
Device Type
0 Acoustic Monitor Transmitter 
1 RTD Transmitter 
2 Pressure Transmitter 
3 Dual 0-10V Input Transmitter 
4 Dual 4-20mA Input Transmitter 
5 Thermocouple 
Transmitter
6 Reserved 
7 Level Sensor Transmitter 
8 Split RTD Transmitter 
9 Split Pressure Transmitter 
10 Split Dual Thermocouple Transmitter 
11 Differential Pressure Transmitter (100 IN. H20) 
12 Split Differential Pressure Transmitter (100 IN. H20) 
13 Differential Pressure Transmitter (300 IN. H20) 
14 Split Differential Pressure Transmitter (300 IN. H20) 
15 Differential Pressure Transmitter (25 PSID) 
16 Split Differential Pressure Transmitter (25 PSID) 
17 Differential Pressure Transmitter (100 PSID) 
18 Split Differential Pressure Transmitter (100 PSID) 
19 Differential Pressure Transmitter (300 PSID) 
20 Split Differential Pressure Transmitter (300 PSID) 
21 Reserved 
22 Reserved 
23 Gauge and Submersible Level Transmitters 
24 Split Gauge and Submersible Level Transmitters 
25 Advanced 
Development
26 Switch Input Transmitter 
27 Switch Input Transmitter with Output Options 
32