Typical steam coil piping, Water piping, Direct expansion – Heatcraft Refrigeration Products 4346B001 User Manual

Page 3

Advertising
background image

3

Low Pressure Open Gravity Return System

Steam Main

Gate Valve

Typical Steam Coil Piping

Strainer

Control Valve

Union

12” Minimum

Open Vent

Vacuum Breaker

1/2”-15” Check Valve

Gate Valve

Union

Union

Strainer

Dirt Pocket

Return Main

Combination Float

and

Thermostatic Trap

Vent

Steam Main

Gate Valve

Strainer

Control Valve

Union

Vacuum Breaker

1/2”-15” Check Valve

Vent

12” Minimum

Union

Union

Strainer

Dirt Pocket

Return Main

Gate Valve

Float or

Bucket Trap

When two or more steam coils are furnished in a unit,

provide separate traps for each coil. Size traps with

ample capacity using the maximum heating load and

service factor recommended b y the trap manufacturer.

Select control valves in accordance with the

recommendations of the control manufacturer using

actual heating loads.

Install suitable strainer ahead of all automatic valves and

traps to catch dirt and scale. Provide adequate air vents

to expel air and other non-condensable.

Control valves used for Type “J”, “NFS”, “RA” and

“NFD” coils must be gradual acting modulating type with

veeport.

Where a control valve is used for Type “S” or “R” coils

and when the entering air temperature is below 35ºF.,

use a two position valve. Locate control element in the

entering air stream so that valve will remain open with

a minimum of five pounds steam pressure when the

entering air temperature is below 35ºF.

When the system is started up the damper should remain

closed for approximately ten minutes after the steam

valve is opened.

Properly locate all temperature sensing elements at a

point of true average air mixture temperature.

Refer to “Typical Steam Coil Piping Diagrams” for

controls positioning and piping configuration.

When face and bypass dampers are used, it is good

practice to install on the coil a valve which closes as

the face damper closes to prevent over heating due to

damper leakage or heat picked up by the air wiping the

exposed coil face.

Water Piping

All piping must be supported independent coils.

Swing joints or flexible fittings must be provided to absorb

expansion and contraction strains. Rigid piping may also

reduce effectiveness of vibration isolators.

The water supply should always be connected to the

bottom inlet of the coil. The coil connections are identified

with stickers.

Water coils , 3 through 10 rows, are supplied with a vent

and drain connection (1/4” MPT) which extends through

the unit casing.

For protection of coils exposed to freezing temperatures,

refer to page 6.

Coils must be adequately vented in order to prevent air

binding.

Direct Expansion

Both the liquid distributor and the suction line extend

through the casting.

The expansion valve utilized must be of the external

equalizer tube type. The expansion valve bulb must be

located on the suction line between the coil and the 1/4”

external equalizer tube. Never locate the bulb in a trap.

All refrigerant piping practices used should be in

accordance with local codes and latest ANSI Standard

B9 Safety Code. Hard drawn type “L” or “K” copper tubing

should be used. Soft tubing where bending is required

may be used provided it is protected in accordance with

local code restrictions.

Good Practice should be followed as to pulling adequate

vacuum, tubes cleaned of foreign material, etc.

High Pressure System

Advertising