Water coils exposed to freezing temperature, Draining coils using supplemental air blower, Installation of anti-freeze solution – Heatcraft Refrigeration Products 4346B001 User Manual

Page 6

Advertising
background image

6

Water Coils Exposed

to Freezing Temperature

Water coils exposed to freezing temperatures must be

protected from freeze-up by either adding anti-freeze

solution to coils or proper draining of the coils.

The coils are circuited so that there are no trapped

circuits. However, because of the serpentine nature of

the circuiting, it is almost impossible to adequately drain

the coils by gravity alone. Particularly on longer coils,

even a fraction of a degree deviation from a horizontal

plane can lead to water being trapped within the

serpentine.

Water that failed to drain from a single tube,

or even part of a tube, can cause the tube to

rapture upon freezing.

Draining Coils Using Supplemental

Air Blower

Ideally, a blower capable of delivering 150 CFM of air

at approximately 40-50 inches of water or more should

be used. Some small air compressors, while delivering

higher pressures, probably will not deliver sufficient

volume of air and this is equally as important.

1. Drain the coils by gravity after opening the

supply, return, vent and drain connection.

2. Connect the blower to large connection that

is at the greatest elevation. The small vent or

drain connection on the header to which the

blower is connected should be closed.

Refer to Figure 1 for typical hook -up during the

blow-out operation.

It is helpful to tap the coil causing along the

length of the coil during the draining process.

The blower should be operated until no moisture

can be detected leaving the coil. Then, shut the

blower off and permit the coil to stand for a few

minutes. This will permit the moisture that has

adhered to the walls to accumulate. Then the

blowing out operation should be repeated.

Ideally, the coil should be permitted to stand

twenty-four (24) hours and blown out again.

3. Leave all connections open until coil is put into

operation.

Installation of Anti-Freeze Solution

A second way to prevent a coil freeze-up is to add an

anti-freeze to the coil, such as industry inhibited glycol.

The coil should be valved off so that only the coil would

have anti-freeze added to it. The most positive way to

assure the mixing of the anti-freeze is to make a run-

around loop with a circulating pump.

1. Open all connections and drain the coil as

thoroughly as possible.

2. The anti-freeze solution should be added to the

coil and circulated through the coil until the

solution is thoroughly mixed and all air is purged

from the coil. The air vent should be opened

during the filling operation and cracked during the

pumping operation to accomplish this. When

the solution has circulated for 15-20 minutes,

the concentration of the solution should be

checked with suitable hydrometer. If the

concentration is low, add more glycol and

operate the pump again. A typical piping diagram

is shown in Figure 2.

3. The anti-freeze solution may then be left in

the coils or drained and used to flush another

coil. The concentration must be checked for each

coil flushed.

The adding of anti-freeze to a system exposed to

freezing conditions may be necessary if the system

must be operation at a moment’s notice. This affects

the chiller and coil performance and must be taken into

consideration when selection the components.

Note: Most anti-freeze solution will be furnished with

a chart of concentration at freezing point. It is also

important to be certain that the anti-freeze solution

used is not corrosive to the tubing.

Advertising