3) Allow the vacuum pump to pull down to a 29.9" Hg vacuum. Evacuating period depends

on pump capacity.

4) Close both gauge manifold valves.
5) Turn off the vacuum pump. Disconnect the vacuum pump hose and attach it to a

refrigerant service cylinder. Remember to loosen the connection, and purge the air
from the hose. See the nameplate for the required refrigerant charge. Hoshizaki
recommends only virgin refrigerant or reclaimed refrigerant which meets ARI Standard
No. 700 (latest edition) be used.

6) A liquid charge is recommended for charging an R-404A system. Invert the service

cylinder and place it on scales.

7) Open the high-side gauge manifold valve and allow the system to charge with liquid

until the proper charge is met.

8) If necessary, add any remaining charge to the system through the compressor access

valve. Use a throttling valve or liquid dispensing device to add the remaining liquid
charge through the compressor access valve with the unit running.

9) Back out the receiver service valve stem all the way and tighten. Disconnect the gauge

manifold hoses.
Note: Be sure the receiver service valve stem is backseated all the way out and tight

before disconnecting the gauge manifold hose.

10) Cap the valves to prevent possible leaks.

Fig. 1

Rail Refrigerant Tubes

Rail Low-Side Service Valve

Rail High-Side Service Valve

Hex Head Bolt

Cabinet Liquid Line Valve

Cabinet Expansion Valve

Rail Expansion Valve

Rail High-Side
Access Valve

Rail Low-Side
Access Valve

Compressor
Access Valve

Rail Service Valve Bracket

Power Switch

Receiver Service Valve

Rail Cooling Switch

Wire Cover

Upper Attachment Nut
and Washer

Lower Attachment Nut
and Washer

Power Cord

Rail Liquid Line Valve

Compressor

Receiver Tank

Condenser

Drier