Hoshizaki REFRIGERATED PREP TABLE WITH RAISED RAIL 73168 User Manual

Page 45

Advertising
background image

45

16) Once the repair is made, replace the refrigeration cartridge back into its correct

position. Support the cabinet evaporator as it enters the cabinet evaporator case.

17) Reconnect the rail side refrigerant tubes. Use a backup wrench and tighten the fittings

1/6 turn beyond fully seated. Use a backup wrench when tightening the fittings.

18) Secure the rail service valve bracket back in its correct position.
19) Secure the refrigeration cartridge with the attachment nuts, washers, and the hex head

bolt.

20) Replace the wire cover and panels in their correct positions.
21) Connect the high-side gauge manifold hose to the rail high-side access valve.
22) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of

refrigerant to the system (if using an electronic leak detector), and then raise the
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with
pressurized air for leak testing

23) Evacuate the rail system. Close the gauge manifold valves.
24) Open the rail high and low-side service valves. Back out the rail high and low-side

service valve stems all the way until fully seated.
Note: Be sure the rail high and low-side service valve stems are backseated all the way

out and tight.

25) Remove the gauge manifold hoses.
26) Cap the valves to prevent possible refrigerant leaks.
27) Use an electronic leak detector or soap bubbles to check the rail refrigerant

connections for refrigerant leaks.

28) Reconnect the power supply cord connector, rail thermistor connector, and the

perimeter heater/rail fan connector.

29) Plug the unit back in, then move the power switch to the "ON" position to start the unit's

cooling process.

Advertising