Caution, Maintenance, Every 1 to 3 months (depending on water quality) – Honeywell ENVIRACAIRE HE365B User Manual

Page 7: End of humidification season

Advertising
background image

HE365A,B POWERED FLOW-THROUGH HUMIDIFIER

68-0243

7

Table 1. Recommended Humidity Control Settings.

Table 2. Recommended Frost Factor Adjustment.

MAINTENANCE

A regular maintenance program prolongs the life of the
humidifier and provides a more comfortable environment.
Frequency of cleanings depends on water conditions.

Either hard or soft water can be used in the humidifier, but
hard water mineral deposits are more difficult to clean then
soft water deposits.

Use the following procedure to clean the humidifier.

CAUTION

Personal Injury or Equipment Hazard.
Power Supply can cause electrical shock or
equipment damage.
Disconnect power supply before performing humidifier
maintenance.

IMPORTANT

Never oil any part of the humidifier.

Every 1 To 3 Months
(Depending on Water Quality)

1. Disconnect the power and turn off the humidifier water

supply.

2. Remove the humidifier cover. See Fig. 11.

Outside Temperature

Recommended Setting

Outside Temperature

Recommended Setting

-20°F (-29°C)

15

+10°F (-12°C)

30

-10°F (-23°C)

20

+20°F (-7°C)

35

0°F (-18°C)

25

+20°F (-7°C)

40

Humidity Level

Recommended Setting

Insufficient humidity

Increase the frost factor dial be one setting

Condensation on windows

Reduce the frost factor dial by one setting.

3. Remove the humidifier pad assembly from the humidifier

by grasping the tray and pulling it toward you.

4. Pull one side of the humidifier pad assembly frame

toward you and remove the tray from the frame.

5. Gently pinch the water nozzle catches inward until the

water nozzle can be lifted off the tray.

6. Slide the humidifier pad out of the frame.
7. Carefully scrape any mineral deposits from the tray and

frame. Be sure the frame drain hole has nothing
blocking it.

8. Check the humidifier pad and if excessive mineral

deposits are present, replace with a new HC26E
Antimicrobial Pad.

9. Disconnect the drain hose from the drain fitting on the

bottom of the humidifier housing.

10. Clean the drain fitting, if necessary.

11. Bend the drain hose to loosen any mineral deposits.

12. Flush the drain hose with pressurized water (a running

tap) to clean the hose.

13. Reattach the drain hose to the drain fitting.
14. Slide the humidifier pad back into the frame.

I

IMPORTANT

To maintain the antimicrobial properties of the
humidifier, use only a Honeywell HC26E
Antimicrobial Pad. Be sure the marked side of the
antimicrobial humidifier pad is facing up for proper
performance.

15. Reattach the tray to the frame.
16. Snap the water nozzle back on the tray.
17. Place the antimicrobial humidifier pad assembly in the

humidifier housing and press until the assembly is
seated.

18. Be sure the water feed tube is placed in the guide slots

of the humidifier housing.

19. Replace the humidifier cover.
20. Verify the humidifier operation by following the steps in

the Checkout Procedure section.

End of Humidification Season

The humidifier needs to be cleaned and shut off at the end of
the heating season. Follow steps 1 through 19 from the Every
1 To 3 Months section.

IMPORTANT

Be sure the humidifier power is off.

Fig. 11. Location of humidifier parts.

M14671

COVER
ASSEMBLY

HUMIDIFIER
PAD ASSEMBLY

FEED TUBE NOZZLE

WATER
DISTRIBUTION TRAY

HUMIDIFIER
HOUSING

THUMB
SCREW