G. install outside air kits – Hearth and Home Technologies I100 User Manual

Page 24

Advertising
background image

24

Outlet placed

higher than 3 ft

below the

termination cap

Attic space

Garage or

combustible

liquids storage

Outlet blocked by

snow, leaves, etc.

Clear area

outside

house or in

ventilated

crawl space

YES

NO

NO

NO

NO

Factory-built

fireplace

Use only duct materials specified by manufacturer (preferably

with short run or mainly straight duct, except small dip for cold

air trap which will help prevent flow of cold air).

Figure 7.18 Outside Combustion Air Placement

))))

))))))))))))))))))

))

)))))))

))))

)))

))))

))))

))))

)))

))))

))))

))))

))))

)))

)))

))))

))))

)))

))))

)))))))

3 ft min. from

top of uppermost

chimney section

to air inlet.

G. Install Outside Air Kits

• Refer to Figures 7.17 through 7.21.

• Keep duct runs short and straight to minimize

restriction. A small dip is acceptable for a cold air

trap.

• The outside air kit must be installed on both sides of

the fireplace.

• Locate the outside air hoods in a clear area, preferably

into prevailing wind during the heating season. Refer

to Figure 5.2 and Figure 7.18.

• The air duct may be run vertically.

- The outside air hood must be at least 3 ft (.91 m)

below the top of the uppermost chimney section

as shown in Figure 7.17.

Figure 7.15 Slide Grate Retaining Bracket into Notch

• Slide grate retainers into notches in bottom of back

refractory on each side as shown in Figures 7.15 and

7.16. Place one on each side of back refractory.

Figure 7.16 Grate Retaining Bracket in Place

• Replace hearth stone.

• Place grate into fireplace and slide back legs into

brackets to hold grate in place.

• Repalce smoke shield and screen assemblies.

CAUTION! Risk of Fire or Asphyxiation! DO NOT draw out-

side combustion air from wall, floor or ceiling cavity, or enclosed

spaces such as an attic or garage.

DO NOT place outside air hood close to exhaust vents or

chimneys. Fumes or odor could be drawn into the room

through the fireplace.

• Locate outside air inlet to prevent blockage from leaves,

snow/ice, or other debris. Blockages could cause combustion

air starvation.

Heatilator • I100 • 35144 • Rev AG 7/12

Figure 7.17 Possible Outside Air Inlet Locations

Advertising