Section 3: installing the fireplace – Heat & Glo Fireplace PIER-TVFL st-42tvfl User Manual
Page 8
14
Figure 3. Fireplace Locations and Space
Requirements
Clearance Requirements
The top, back, and sides of the fireplace are defined
by stand-offs.
Minimum Clearances from the Fireplace to
Combustible Materials
Glass
Back of
Metal Ends
Top of
Sides
Floor
Fireplace
of Fireplace
Fireplace
Ceiling*
36 inches
0
1/2 inch
1/2 inch
4-1/2 inches
31 inches
(914 mm)
(13 mm)
(13 mm)
(89 mm)
(787 mm)
The clearance to the ceiling is measured from the top of
the unit, excluding any standoffs (see Figure 13).
The minimum clearance to a perpendicular wall extending
past the face of the fireplace is one inch (25 mm).
The metal end(s) of these fireplaces may NOT be
recessed into combustible construction.
3
Installing the
Fireplace
Step 1
Locating the
Fireplace
The diagram below shows space and clearance
requirements for locating a fireplace within a room.
PIER-TVFL
ST-42TVFL
36 "
GLASS
GLASS
GLASS
36"
GLASS
GLASS
1"
36"
TOP
VIEW
*