Section 3: installing the fireplace – Heat & Glo Fireplace PIER-TVFL st-42tvfl User Manual

Page 8

Advertising
background image

14

Figure 3. Fireplace Locations and Space
Requirements

Clearance Requirements

The top, back, and sides of the fireplace are defined
by stand-offs.

Minimum Clearances from the Fireplace to

Combustible Materials

Glass

Back of

Metal Ends

Top of

Sides

Floor

Fireplace

of Fireplace

Fireplace

Ceiling*

36 inches

0

1/2 inch

1/2 inch

4-1/2 inches

31 inches

(914 mm)

(13 mm)

(13 mm)

(89 mm)

(787 mm)

The clearance to the ceiling is measured from the top of
the unit, excluding any standoffs (see Figure 13).

The minimum clearance to a perpendicular wall extending
past the face of the fireplace is one inch (25 mm).

The metal end(s) of these fireplaces may NOT be
recessed into combustible construction.

3

Installing the
Fireplace

Step 1
Locating the
Fireplace

The diagram below shows space and clearance
requirements for locating a fireplace within a room.

PIER-TVFL

ST-42TVFL

36 "

GLASS

GLASS

GLASS

36"

GLASS

GLASS

1"

36"

TOP

VIEW

*