Malfunctions, causes, remedy

Troubleshooting also with Opus (Order No. 204-80-70) or PC
software in the menu

Keyboard check: keys of the membrane keyboard.

Output functions: functions XO...Y3, check if box
provides current for valves.

Hydraulic accumulator: functions of the hydraulic
accumulator.

Specified value channel.

FCE1: Joystick functions.

Diagnosis of master inputs.

Diagnosis of BKN nodes.

Malfunction

Cause

Remedy

No build-up of pressure

Slide valve in input plate is stuck
(foreign particles)

Remove, clean or plate replace the
slide valve

Strong flow rate fluctuation or too little
flow of priority flow valve I

Low oil flow

Increase RPM, reduce consumption of
2nd load