T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER

62-0255—07

18

Fig. 36. Setup - Outputs - Modulating Output Menu.

1.3.1. Setting up the Modulating Outputs

1. From the Output menu, use the S and T buttons to

highlight the desired modulating output (MOD 1 or
MOD 2).

2. Press the X button to display the selected MOD

menu.

Use the remaining procedures, beginning with “1.3.1.1.
TYPE (of output signal)”, to set up each modulating
output. If you have two modulating outputs, repeat these
procedures for each modulating output.

Fig. 37. Setup - Outputs - Mod Out - Type.

1.3.1.1. TYPE (of output signal)

1. From the Mod menu, use the S and T buttons to

highlight TYPE.

2. Press the X button to display the Type selections.
3. Use the Sand T buttons to highlight the desired

output type.

Default: 4-20 mA

4. Press the X button to accept the selected type and

return to the Mod menu.

Fig. 38. Setup - Outputs - Mod Out - Minimum Output

Percentage.

1.3.1.2. MIN OUT %

The minimum output % prevents the output from dropping
below the value entered. This value can be useful to
maintain minimum damper position.

Using the time clock or digital input to disable the output
forces the output to 0%.

1. From the Mod menu, use the S and T buttons to

highlight MIN OUT %.

2. Press the X button to display the Min Out %.
3. Use the S and T buttons to increase/decrease the

desired value from 0% to 100% in 1% increments.

Default: 0%
Range: 0 to 100%

4. Press the X button to accept the percentage and

return to the Mod menu.

Fig. 39. Setup - Outputs - Mod Out - Integral.

1.3.1.3. INTEGRAL

1. From the Mod menu, use the S and T buttons to

highlight INTEGRAL.

2. Press the X button to display the Integral seconds.
3. Use the S and T buttons to increase/decrease the

value from 0 to 3,600 in 10 second increments.

Default: 400 seconds
Range: 0 to 3,600 seconds

4. Press the X button to accept the seconds and

return to the Mod menu.

See the Notes on page 19 for Integral timing information.

SETUP

OUTPUTS

MOD

1

SETUP

OUTPUTS

MOD 1

TYPE

MIN OUT %

INTEGRAL

DERIVATIV

SCHEDULE

RESET

EXIT

M24599

SETUP
OUTPUTS
MOD

1

TYPE

SETUP

OUTPUTS

MOD 1

TYPE

SELECT

TYPE FOR

MOD 1

4 - 20 mA

0-10 V

2-10 V

SERIES 90

M24600

SETUP

OUTPUTS

MOD 1

MIN OUT %

ENTER

MINIMUM

PERCENT FOR

MOD 1

SETUP

OUTPUTS

MOD 1

MIN OUT %

0

%

M24601

SETUP

OUTPUTS

MOD 1

INTEGRAL

ENTER

INTEGRAL

TIME FOR

MOD 1

SETUP

OUTPUTS

MOD 1

INTEGRAL

400

SEC

M24602