Program menus for outputs with reset, Sp max a1 or boiler max, Reset b1 or outsd min – Honeywell T775U User Manual

Page 29

Advertising
background image

T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER

29

62-0255—07

Fig. 65. Reset Curve for MOD 1 with Setback Offset.

NOTE: For MOD 2 and the Relays, a setpoint offset is

used. See “3.3.1. SETPOINT OFFSET (MOD 2
only)” on page 32.

The remainder of this section beginning with “3.2.
Program Menus for Outputs with Reset” on page 29
describes the individual parameters for configuring
outputs with Reset.
For your reference, the following Reset programming
procedure uses the values in Fig. 65 above.

Fig. 66. Setpoint Values for Reset and Setback.

3.2. Program Menus for Outputs with
Reset

Press the MENU button, select PROGRAM, then highlight
MOD 1 and press the X button to view the parameters.
The Reset curve settings (Fig. 67 through Fig. 70) are
programmed for the first output (MOD 1) and these
settings apply to all outputs that are configured for Reset.
See Fig. 65 for the reset curve values used in the
following section.

NOTE: The Setback parameter displays only if schedul-

ing is enabled (see Fig. 47 on page 21) or the DI
Option is set to Setback (see Fig. 49 on
page 22).

Fig. 67. Program - Sensor A Max. Setpoint.

3.2.1. SP MAX A1 or BOILER MAX

(Setpoint maximum for Sensor A)

1. From the menu, use the S and T buttons to high-

light BOILER MAX or SP MAX A1.

2. Press the X button to display the maximum setpoint

value.

3. Use the S and T buttons to increase/decrease the

desired maximum setpoint temperature.

Default: 180°F (82°C)
Range: -40°F to 248°F (-40°C to 120°C)

4. Press the X button to accept the setpoint tempera-

ture and display the next option.

Fig. 68. Program -Sensor B Max. Setpoint.

3.2.2. RESET B1 or OUTSD MIN

(Sensor B value when at SP MAX A1 Setpoint)

1. From the menu, use the S and T buttons to high-

light RESET B1 or OUTSD MIN.

2. Press the X button to display the setpoint value.
3. Use the S and T buttons to increase/decrease the

desired setpoint temperature.

Default: 10°F (-12°C)
Range: -40°F to 248°F (-40°C to 120°C)

4. Press the X button to accept the value and display

the next option.

SENSOR B

SP MAX A1

(BOILER MAX)

SP MIN A2

(BOILER MIN)

200

140

10

SETBACK

OFFSET

-10°F

190

20

30

40

50

60

70

°F

80

150

160

170

210

220

180

°F

RESET B1

(OUTSD MIN)

RESET B2

(OUTSD MAX)

S

E

N

S

O

R

A

M24570

SP MAX A1

RESET B1

SP MIN A2

RESET B2

THROT RNG

ACTION

SETBACK

EXIT

OR

PROGRAM

MOD 1

MENU

PROGRAM

MOD 1

BOILR MAX

OUTSD MIN

BOILR MIN

OUTSD MAX

THROT RNG

ACTION

SETBACK

EXIT

MENU

PROGRAM

MOD 1

MOD 1 RESET:

YES-OTHER AND

DI OPTION = SETBACK

MOD 1 RESET:

YES-BOILER AND

DI OPTION = SETBACK

M24571

ENTER

MAXIMUM

SETPOINT FOR

SENSOR A

PROGRAM
MOD

1

SP

MAX

A1

MENU

PROGRAM

MOD 1

SP MAX A1

210

F

o

M24572

ENTER

SENSOR B VALUE

FOR MAXIMUM

SETPOINT

PROGRAM
MOD

1

RESET B1

MENU

PROGRAM

MOD 1

RESET B1

20

F

o

M24573