T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER

25

62-0255—07

2. PROGRAMMING OUTPUTS
(MOD AND RELAY) WITH NO
RESET

The T775U can be programmed for Reset or No Reset.
From the factory, the T775U is programmed for No Reset.
This section describes the steps necessary to program
the controller for No Reset.

NOTE: For applications where Reset is not used, only

one sensor (Sensor A) is available for use.

Fig. 57. Program Menu.

2.1. Entering Program Mode

Press the MENU button, then select PROGRAM and
press the X button to view the Program menu.

Fig. 58. Program Menu - No Reset.

2.1.1. Program Menu for Outputs with
No Reset

From the Program menu, select MOD 1, MOD 2,
RELAY 1, or RELAY 2 to view the parameters. This
section illustrates the screens for selecting MOD 1, but
other than as noted below, the programming is the same
for each output.

NOTE: For Relays, DIFFRNTL replaces THROT RNG.

NOTE: The Setback parameter displays only if schedul-

ing is enabled (see Fig. 47 on page 21) or the DI
Option is set to Setback. (see Fig. 49 on
page 22).

Continue with “2.1.2. SETPOINT”.

Fig. 59. Program - Setpoint.

2.1.2. SETPOINT

1. From the menu, use the S and T buttons to high-

light SETPOINT.

2. Press the X button to display the setpoint value.
3. Use the S and T buttons to increase/decrease the

desired setpoint temperature.

Default: 70°F (21°C)
Range: -40°F to 248°F (-40°C to 120°C)

4. Press the X button to accept the setpoint tempera-

ture and display the next option.

MENU

PROGRAM

MENU

PROGRAM

MOD 1

MOD 2

RELAY 1

RELAY 2

EXIT

M24567

PROGRAM

MOD 1

MENU

PROGRAM

MOD 1

SETPOINT

SETBACK

SENSOR

THROT RNG

ACTION

EXIT

M24580A

ENTER

SETPOINT

FOR

MOD 1

PROGRAM
MOD

1

SETPOINT

MENU

PROGRAM

MOD 1

SETPOINT

70

F

o

M24581