Application Data

Liquid Level: Closed Tank
Determine the minimum and
maximum pressure differentials to
be measured (Figure 17).

PMin = (SGp x a) - (SGf x d)
= LRV when HP at bottom of

tank

= –URV when LP at bottom of

tank


PMax = (SGp x b) - (SGf x d)
= URV when HP at bottom of

tank

= –LRV when LP at bottom of

tank


Where:


minimum level = 4mA

maximum level = 20 mA

a = distance between bottom tap

and minimum level


b = distance between bottom tap

and maximum level


d = distance between taps

SGf = Specific Gravity of capillary

fill fluid (See Page 9 for

values.)

SGp = Specific Gravity of process
fluid



b

a

LP

HP

24253

Max

Level

Min

Level

¥ Transmitter above datum

LP

HP

b

a

Max

Level

Min

Level

¥ Transmitter at datum

LP

HP

b

a

Max

Level

Min

Level

¥ Transmitter below datum

Figure 17—Closed tank liquid level measurement distances