Chimney connector, Chimney height/draft, Connection to masonry chimney – Heat & Glo Fireplace WS-250 User Manual

Page 8: Connection to a masonry chimney

Advertising
background image

8

CHIMNEY CONNECTOR

The chimney connector must be 6" (152mm) diam-

eter with a minimum thickness of 24 gauge. Do not

use aluminum or galvanized steel. They cannot prop-

erly withstand the extreme temperatures of a wood

fire. Do not use chimney connector pipe as a chim-

ney. You must connect your stove to a chimney com-

parable to those illustrated in this manual.

Chimney connector sections must be attached to the

stove and to each other with the crimped end toward

the stove (see Figure 6). This allows creosote to run

into the stove and not onto the outside of the pipe.

Attach the chimney connector to the flue collar with

three sheet metal screws. All joints should also be

secured with three sheet metal screws. Otherwise,

in the event of a creosote fire, the connector may vi-

brate apart.

For proper operation, the chimney connector should

be as short as possible. Horizontal lengths of chimney

connector should have a minimum upward slope from

the stove of at least ¼" per foot.

CHIMNEY HEIGHT/DRAFT

To insure that the stove burns properly, the chimney

draft (static pressure) should be approximately 0.1"

water column (W.C.) during a high burn and .04" W.C.

during a low burn, measured 6" (152mm) above the

top of the stove after one hour of operation at each

burn setting.

NOTE: These are guidelines only, and may vary

somewhat for individual installations.

This stove was designed for and tested on a 6"

(152mm) chimney, 12'-14' (3.66-4.27m) high,

FIGURE 6

measured from the top of the stove. The further your

stack height or diameter varies from this configuration,

the probability of performance problems increases.

In addition, exterior conditions such as roof line,

surrounding trees, prevailing winds and nearby hills

can influence stove performance.

CONNECTION TO A MASONRY

CHIMNEY

1. CHIMNEY:

Should the stove be connected to a masonry

chimney, the chimney should be examined for cracks,

loose mortar, or other signs of deterioration and

blockage. The stove should not be installed until it is

determined that the chimney is safe for use. Since

an oversized flue contributes to the accumulation of

creosote, the size of the flue should be checked to

determine that it is not too large for the stove. The

chimney should also be checked to insure it meets

the minimum standards of the National Fire Protection

Association (NFPA) Standard 211. Following is a list

of the more critical minimum requirements for a

properly constructed chimney.

The masonry wall of the chimney, if brick or modular

block, must be a minimum of 4" (102mm) thick. A

mountain or rubble stone wall must be at least 12"

(305mm) thick.

The chimney must have a fire clay flue liner (or

equivalent) with a minimum thickness of 5/8" (16mm)

and must be installed with refractory mortar. There

must be at least ½ " (13mm) air space between the

flue liner and the chimney wall (see Figure 7). An

equivalent liner must be a listed chimney liner system

or other approved material.

FIGURE 7

Advertising
This manual is related to the following products: