Heat & Glo Fireplace ST-38HV-AU User Manual

Page 15

Advertising
background image

15

For Vertical Runs
The flue system must be supported every eight
(8) feet (2.4M) above the heater flue outlet by wall
brackets.

To install support brackets for vertical runs:
• Attach wall brackets to the flue pipe and se-

cure the wall bracket to the framing members
with nails or screws.

Use wall brackets to support vertical runs every
8 feet (2.4M) above the heater flue outlet.

Figure 13 Installing Support Brackets

4. Install Firestops

For Horizontal Runs - Firestops are REQUIRED
on both sides of a combustible wall through which
the flue passes.

To install firestops for horizontal runs that pass
through either interior or exterior walls:

• Cut a 12-inch by 12-inch (305 mm X 305 mm)

hole through the wall. The center of the hole
is one (1) inch (25mm) above the center
of the horizontal flue pipe.

• Position the firestops on both sides of the hole

previously cut and secure the firestops with nails
or screws.

• The heat shields of the firestops MUST BE

placed towards the top of the hole.

• Continue the flue run through the firestops.

Figure 14 Hole and Flue Pipe

Figure 15 Heat Shield, Interior and Exterior
Firestops

For Vertical Runs - One ceiling firestop is
REQUIRED at the hole in each ceiling through
which the flue passes.

To install firestops for vertical runs that pass through
ceilings:

• Position a plumb bob directly over the center of

the vertical flue component.

• Mark the ceiling to establish the centerpoint of

the flue.

FLUE PIPE

1 INCH MIN.

(25.4mm)

FLUE

OUTLET

WALL BRACKET

WALL STUD

8 FT.

(2.4m)

TRIM HEAT
SHIELD IF TOO
LONG, ADD TO
SHIELD IF TOO
SHORT

EXTERIOR
FIRESTOP

INTERIOR

FIRESTOP

HEAT SHIELD