Ip m, Clearances – Heat & Glo Fireplace ST-38HV-AU User Manual

Page 7

Advertising
background image

7

NOTES:

1. All distances are measured vertically or horizontally along the wall to a point

in line with the nearest part of the terminal.

2. Prohibited area below electricity meter or fuse box extends to ground level.
3. See clause 5.13.6.6 for restrictions on a flue terminal under a roofed area.
4. See Appendix J, Figure J1(a) and J2(a) for clearances required from a flue

terminal to a LP Gas cylinder. A flue terminal is considered to be a source of ignition.

MINIMUM CLEARANCES REQUIRED FOR BALANCED FLUE TERMINALS

OR THE FLUE TERMINALS OF OUTDOOR APPLIANCES

Figure 4

T = Flue terminal

M =

Gas meter

Shading indicates prohibited

I = Mechanical air inlet

P =

Electricity meter

areas for flue terminals

or fuse box

a

-

Below eaves, balconies or other projections: MIN. CLEARANCE(mm)

Appliances up to 50 MJ/h input ........................................................................................... 300
Appliances over 50 MJ/h input ............................................................................................ 500

b

-

From the ground or above a balcony ...................................................................................... 300

c

-

From a return wall or external corner ..................................................................................... 500

d

-

From a gas meter (M) ........................................................................................................... 1000

e

-

From an electricity meter or fuse box (P) ............................................................................... 500

f

-

From a drain or soil pipe ......................................................................................................... 150

g

-

Horizontally from any building structure (unless appliance approved
for closer installation) or obstruction facing a terminal ......................................................... 500

h

-

From any other flue terminal, cowl, or combustion air intake ............................................... 500

j

-

Horizontally from an openable window, door, non-mechanical air
inlet, or any other opening into a building, with the exception of
sub-floor ventilation:

Appliances up to 150 MJ/h input ......................................................................................... 500
Appliances over 150 MJ/h input ........................................................................................ 1500

k

-

From a mechanical air inlet, including a spa blower ......................................................... 1500

n

-

Vertically below an openable window, non-mechanical air
inlet or any other opening into a building, with the exception of
sub-floor ventilation ............................................................................................. See table below

k

j

j

j

h

t

e

h

h

t

g

DOOR

OPENABLE

WINDOW

k

SEE NOTE 2

d

b

d

a

c

g

SEE NOTE 3

t

e

n

c

f

I

P

M

CLEARANCES

Space Heaters

All other Appliances

Up to 50 MJ/h

Input

150

Up to 50 MJ/h

Input

500

Over 50 MJ/h and

up to 150 MJ/h Input

1000

Over 1 50 MJ/h

Input

1500