Save These Instructions

Oakleaf Woodburning Stove

Dry Seasoned Wood Only!

3-90-798_R9

oakleaf to flue fireplace Conversion (minimum nfpa 211 liner Connection)

notiCe: when using rear flue configuration, a new upper rear heat shield, #1-00-797066 must be installed in

place of the existing shield.
The Chimney Connector shall Not pass Through an attic or Roof space, Closet or similar Concealed space, a

floor or Ceiling.

flue liner with required

air space

stainless steel Chimney

Connector Must Extend

to flue liner

Minimum 8" Masonry

thickness in front of

smoke Chamber

use damper adapter

or seal with Non-

Combustible material

airtight

insulated

Clean-Out

damper plate

is Removed or

fastened in open

position

listed fireplace

Trim protection for

Reduced Clearance

floor protection*

Combustible floor

*floor protection in accordance with solid fuel appliance listing