Hyundai Ductless Split System

14

• Use a dedicated circuit breaker for the air conditioner(s).

• When connecting the indoor unit(s) to the outdoor unit

please be sure to connect the same number on the
indoor and outdoor unit terminal blocks.

• Be sure to use approved connecting wire (14 gauge

minimum).

• When installing the air conditioner, please be sure to

use the right power supply cable conforming to Cana-
dian Electrical Code/National Electrical Code.

NOTE: Interconnecting voltage is 208/230V.

• The air conditioner always requires grounding.
• Grounding must conform to local regulations.

CONNECTING THE CABLE

!

CAUTION

!

CONNECTING OF POWER SOURCE

Before supplying the power, check that the voltage is within

+6% of the rated voltage marked on the indoor unit label(s).

• Connect one end of the ground wire to the outdoor
unit ground terminal.

• Use minimum 14 AWG wire conductors between the in-

door and outdoor units.

• Refer to page 16 to determine the wire size from the power

supply to the condenser.

!

CAUTION

!

Make sure wire connections are secure otherwise elec-
trical malfunction may occur.

Cool and Heat Model

HYUNDAI ELECTRICAL INTER-CONNECT

REVISION “B” PRODUCT

Cool Model

HHW18000/HHW24000

NOTE: Gnd is Earth Ground
HACW/HACM are cooling only indoor units
HCCW/HCCM are cooling only outdoor units
HAHW is heat pump indoor unit
HCHW is heat pump outdoor unit

!

CAUTION

!

NOTE: For Multi-zone systems, there are two sets of iden-
tical wiring terminals. Be sure to match each air handler
with its corresponding terminal strip connection. Use above
diagram for each circuit.

HCW9000/HCW12000/HMCW18000/HMCW24000

HHW12000/HMHW18000/HMHW24000

HCW18000/HCW24000