TZ-3 TOTALZONE® ZONE CONTROL PANEL

68-0223-2

8

Fig. 15. Heat pump with auxiliary heat wiring.

.

Fig. 16. Trane XL 1800 with TAYPLUS 103 in restricted mode wiring.

Water Source Heat Pumps

Wire the equipment, as applicable, to the TZ-3 as shown in

Fig. 17. Turn DIP switch number 8 to On for fan on in heat.
Remove the two-stage emergency heat jumper.

W2

W3

M19075

E

W1

W2

E

B

G

R

24V TRANSFORMER

FAN RELAY

REVERSING
VALVE (COOL)

EMERGENCY
HEATING RELAY

2 STAGE
HEATING RELAY

HEAT PUMP CONTROLS

TZ-3

PANEL

EQUIP

R

C

O

G

O

Y1

Y2

COMPRESSOR
RELAY

Y

OUTDOOR CONDENSING UNIT

Y

E

R

W2

W3

T

L

1

2

3

1

4

K2

ODT

5

3

G

O/B C

T8611G2051

TRANE XL1800

CONDENSING

UNIT

VARIABLE

SPEED

GAS

FURNACE

TAYPLUS 103

NOTES:

M19076

W2

W3

E

W1

B

G

R

O

Y1

Y2

TL

TL

2 STAGE

EM HEAT

MODEL TZ-3

HEAT

ZoneMAX

Add-A-Zone

TM

COOL

PURGE

FAN

EM.HT

ZONE 1

OVERRIDE

PURGE

ON

1

L

W2

G

Y

R W M6 M4 M1

THERMOSTAT

MOTOR

2 3 4 5 6 7 8

ZONE 2

L

W2

G

Y

R W M6 M4 M1

THERMOSTAT

MOTOR

ZONE 1

AZ1

AZ2

15 MINUTES

10 MINUTES

5 MINUTES

20 MINUTES

25 MINUTES

30 MINUTES

STAGE TIMER

130 F

MAXIMUM

TEMPERATURE

120 F

110 F

140 F

150 F

160 F

1. DIP SWITCHES 6 OFF AND 7 ON.
2. DIP SWITCHES 1 OFF AND 5 ON.
3. T8011R OR T8411R MAY ALSO BE USED.
4. REMOVE THE 2 STAGE EM HEAT JUMPER.

F

Y2

R

B

Y1

O

X2

G

W2

W1

B

O

Y

YLO

BK

R

Y3

X3

G3

Y2

G1

X2

Y1

B

W1