30kw or more, Fig. 2-3-9 fan power switching – Fuji Bikes FRENIC 5000G11S/P11S User Manual

Page 23

Advertising
background image

2-11

M

CN RX TX

L1/R

L2/S

L3/T

Magnetic
contactor

Noise filter

MCCB

Power supply

R0

T0

P1

P(+)

Jumper (not supplied for inverter of 75kW or more)

Fan

U

V

W

N(-)

C

F

Inverter

CN RX TX

R0

T0

When switched to DC power input mode

+

30kW or more

Fig. 2-3-9 Fan power switching

30kW or more

M

P1

P(+)

N(-)

CN RX TX

+

C

L1/R

L2/S

L3/T

R0

T0

Fan

U

V

W

F

Inverter

Switch CNRXTX to the R0-T0 side.

+

Power supply

R

S

T

P(+)

N(-)

PWM converter

C

Fig. 2-3-10A Example of connection by combination with power regeneration converter(40HP or more)

Note:

To connect the power regeneration converter to an inverter of 30HP or less, do not connect the power supply directly to the auxiliary control-power input
terminals (R0 and T0) of the inverter. However, if such a connection is required, insulate these input terminals from the main power of the power
regeneration converter with an insulation transformer. The connection example of a power regeneration unit is provided in the "Power Regeneration
Unit Instruction Manual".

Magnetic

contactor

Noise filter

MCCB or RCD

Power supply

Insulation Transformer

L1/R

L2/S

L3/T

R1

S1

T1

RHC series

R0

T0

L1/R

L3/T

FRN-G11S

U

V

W

M

Fig. 2-3-10B Example of connection by combination with power regeneration converter (30HP or less)

40HP or more

Jumper (not supplied for inverter of 100HP or more)

40HP or more