Warning – Fuji Bikes FRENIC 5000G11S/P11S User Manual

Page 67

Advertising
background image

5-20

This function switches the torque limit value set in
function codes F40 and F41, and E16 and E17 by an
external digital input signal.

Set value input signal

14


Torque limit
value selected

off

F40 DRV TRQ1
F41 BRK TRQ1

on

E16 DRV TRQ2
E17 BRK TRQ2

Setting range
DRV 20 to 200% ,999
BRK 0, 20 to 200% ,999


Motor operation can be switched from 50Hz commercial

power operation to inverter operation without stopping the

motor by switching the external digital input signal.

Set value

input signal

15

Function

off

on

Inverter operation to line operation (50Hz)

on

off

Line operation to inverter operation (50Hz)

Motor operation can be switched from 60Hz commercial

power operation to inverter operation without stopping the

motor by switching the external digital input signal.

Set value
input signal

16

Function

off

on

Inverter operation to line operation (60Hz)

on

off

Line operation to inverter operation (60Hz)

‹

When the digital input signal goes off, 50 or 60 Hz is

output according to the set value input signal after the

restart waiting time following a momentary power failure

(function code H13). The motor is then directed to

inverter operation.

WARNING

- After the LU(Low Voltage) trip is occurred and reset it,
the inverter will automatically restart because the
operation command is kept by internal sequence.
Accident may result.

When an operation command is input (on), the output

frequency can be increased or decreased by an external

digital input signal.

The change ranges from 0 to maximum frequency.

Operation in the opposite direction of the operation

command is not allowed.

Combination of set

value input signals

18

17

Function selected

(when operation command is on)

off off

Holds the output frequency.

off

on

Increases the output frequency

according to the acceleration time.

on

off

Decreases the output frequency

according to the deceleration time.

on

on

Holds the output frequency.

There are the two types of UP/DOWN operations as

shown below. Set the desired type by setting the

frequency (F01 or C30).

‹

The data "8: UP/DOWN 1" is valid only when the Motor

2 is selected.

Frequency

setting

(F01 or C30)

Initial value

at power

input on

Operation command reentry

during deceleration

8

(UP/DOWN1)

0Hz

Operates at the frequency at reentry.

Frequency


FWD ON
(REV) OFF

9

(UP/DOWN2)

Previous

frequency

Returns to the frequency before

deceleration

Frequency

FWD ON
(REV) OFF



This function allows the data to be changed only when an

external signal is being input, thereby making it difficult to

change the data.

19

Function selected

off

Inhibit data changes.

on

Allow data changes.

Note:
If a terminal is set to value 19, the data becomes unable
to be changed. To change the data, turn on the terminal
and change the terminal setting to another number.

The PID control can be disabled by an external digital

input signal.

Set value
input signal

20


Function selected

off

Enable PID control.

on

Disable PID control

(frequency setting from keypad panel).

UP command [UP]/DOWN command [DOWN]

PID control cancel [Hz/PID]

Related function

H20H25

Switching operation between line and inverter (50Hz) [SW50]

Switching operation between line and inverter (60Hz) [SW60]

Torque limit 2/torque limit 1 [TL2/TL1]

Related function

F40F41

E16E17

Write enable for KEYPAD [WE-KP]

Related function

E01E09

(set value: 11, 35)

Related function

F01, C30