Installing and Maintaining the E1200i System

45

5.

Secure the chassis ground connection first:

a Remove one outer nut and one washer from each of the six studs. One nut should remain, tight on

the stud. If the inner nut is loose, re-tighten it to 25 inch/lbs. maximum.

b Locate the chassis ground connector studs on the PEM front panel (see

Figure 16

). The two

rightmost studs are the ground connection.

c

Install the grounding cable onto the ground studs. The grounding cable must comply with your local
electrical codes in size and color (typically the color is green or green with yellow stripe).

NOTE: Grounding cables must be terminated only with a UL-listed 2-hole lug with 1/4-inch holes on 3/
4-inch spacing (see

Figure 17

).

d Replace the two washers and nuts on the studs.
e With a 7/16-inch box or socket wrench, tighten the nuts (torque should not exceed 25inch/lbs).
f

Connect the opposite end of the grounding cable to the nearest appropriate facility grounding post.

Figure 17 Cable Connector Required for E1200i DC PEM

6.

Connect the -48 VDC and Return cables from each PEM to the remote power sources (circuit breakers
A and B).

a Check that the remote power sources (for example, circuit breakers) are in the OFF position.

b Locate the appropriate studs on the PEM front panel (

Figure 16

).

c

The two leftmost studs on the PEM are the -48 VDC (-) connection. The cable attached to these
studs is typically black.

• The two middle studs are the return (+) connection. The cable attached to these studs is

typically red.

d Install the -48 VDC and Return cables on the studs. The cables should be of the size and color to

comply with local electrical codes.

Note: Power cables must be terminated only with a UL-listed 2-hole lug with 1/4-inch studs with 3/4-inch
spacing (

Figure 19

).

e Replace the washers and nuts on the studs.

f

With a 7/16-inch box or socket wrench, tighten the nuts.

Step

Task (continued)

0.750"

High-s trand-count

conductor

diameter
2 Holes

All meas urements s hown in inches .

fn00105lp

0.267