GE EX2100 User Manual

Page 101

Advertising
background image

EX2100 User’s Guide GEH-6632

Appendix B Ratings and Specifications

••••

B-3

Cabinet Dimensions & Weight
Redundant control with dual PCM
redundant converter in a three-cabinet
lineup

Width 141.74 in (3600 mm)
Height 104.32 in (2650 mm)
Depth 31.5 in (800 mm)

Weight of Converter cabinet

3,600 lbs.

Weight of Total Lineup (Converter,
Control, and Auxiliary cabinets)

5,600 lbs.

Cabinet type, control & auxiliary

NEMA 1 (IEC IP 20), convection cooled

Cabinet type, power conversion

NEMA 1 (IEC IP 20), forced air cooled

Power and Control Cable Access

Entrances from the top and/or bottom

Reliability
MTBF - Mean Time Between Failures

Simplex system 25,000 hrs

MTBF - Mean Time Between Failures

Redundant system 175,000 hrs

MTTR - Mean Time to Repair

Any subsystem 4 hrs

Acoustic
Generated Acoustic Noise (Preliminary)

PCM cabinet approximately 75 dB

Codes and Standards
UL 508C

Safety Standard Industrial Control Equipment

CSA 22.2 No. 14

Industrial Control Equipment

UL 796

Printed Wire Board Assemblies

ANSI IPC

Guidelines

IEC 801-2:1991

Electrostatic Discharge Susceptibility

ENV 50140:1993

Radiated RF Immunity

EN 50082-2:1994

Generic Immunity Industrial Environment

IEC 801-4

Electrical Fast Transient Susceptibility

IEC 1000-4-5

Surge Immunity

IEC 1000-4-6

Conducted RF Immunity

ENV 55011:1991

ISM Equipment Emissions

EN 61010-1

Safety of Electrical Equipment, Industrial Machines

IEC 529

Intrusion Protection Codes/NEMA 1/IP 20

IEEE 421.1

Standard Definitions for Excitation Systems for Synchronous machines

IEEE 421.2

Guide for Identification, Testing, and Evaluation of the Dynamic
Performance of Excitation Control Systems

IEEE 421.3

High-Potential Test Requirements for Excitation Systems

IEEE 421.4

Guide for the preparation of Excitation Systems Specs

IEEE 421.5

Recommended Practice for Excitation Systems for Power Stability
Studies

EN50178/LVD/EMC

CE Compliance

IEEE C57.12.01

General Requirements for Dry-Type Distribution & Power Transformers

IEEE C57.110

Recommended Practice for Establishing Transformer Capability when
supplying Non-Sinusoidal Load Currents

IEEE C57.116

IEEE Guide for Transformers Directly Connected to Generators

IEEE C37.90.1

Surge Withstand Capability (SWC) tests for Protective Relays and Relay
Systems

IEEE C57.18.10

Practices and Requirements for Semiconductor Power Rectifier
Transformers

Advertising