Editing parameters – GE EX2100 User Manual

Page 86

Advertising
background image

5-10

••••

Chapter 5 Diagnostic Interface-Keypad

GEH-6632 EX2100 User’s Guide

2. To view detail on a particular fault, select that fault (listed on the Active Fault

Display screen). The following screen displays.

SELECTED FAULT - PRESS

Low AC V, B

006:40:11.008

Low AC input volts detected on
the field exciter.

3. Reset the faults either of two ways:

- Select Reset Faults Now in the Fault Display screen.
- Press the Reset Faults button.

Ø To view the exciter’s Fault History (a list of previously cleared faults

and fault resets)

This display list may be
multiple screens long.

From the Main Menu, select Fault List, then select Display Fault History.

FAULT HISTORY DISPLAY

0 Cleared

Fault reset

86

Trip

DC Over-current trip.

115 Trip

Bridge 1 Fan 1 BAD

58 Brief

Low AC V

95

Field temp alarm

--- RESET FAULTS NOW ---

Editing Parameters

There are two types of parameters that can be changed using the keypad:

Option parameters lists items (options) for you to select. For example,

True/False is an option parameter.

Numeric parameters lists valid digits that you select to create a number.

Ø To edit a parameter
1. From an exciter Parameters screen, select the parameter that is to be changed.

Parameters

GPT_Vrms

=

<No Value>

VHiTripLev

=

1.2

AFFL

=

100

VFFL

=

100

100.0

TripVHiTrip

=

Trip enabled

This displays either an Option or Numeric parameter screen (see both below) with
the New Value line highlighted.