Astat, Ibp plus service instructions, Troubleshooting guide – GE Industrial Solutions ASTAT-IBP Plus Solid State Starters User Manual

Page 15

Advertising
background image

ASTAT

®

-IBP Plus Service Instructions

Prices and data subject to change without notice.

11

Troubleshooting Guide

This guide is provided for troubleshooting and isolating common problems. It does not cover every possible situation.

Contact the Customer Support Center at 800-843-3742 if any problem is not resolved by these procedures.

S y m p t o m o r E r r o r & ( E r r o r C o d e )

S y m p t o m o r E r r o r & ( E r r o r C o d e )

Possible Cause

Possible Cause

M e a s u r e s t o B e T a k e n

M e a s u r e s t o B e T a k e n

No control voltage.

Main breaker tripped or fuse blown

Check wire harness and control voltage

F1 fuse blown on power supply PCB

Check and change.

Display OFF

Bad connection of flat ribbon wire

joining power supply PCB to control

PCB

Verify connectors.

Check power supply board and logic

board for 5VDC. Use a DC voltmeter on

the power supply board, (-) lead of

voltmeter on the top lead of C6 (located

next to the black heatsink on the right

edge of the power supply board) and the

(+) lead of voltmeter on top lead of Diode

AD21 or R25 (located on the upper right

corner of the power supply board.)

Equipment does not respond to STOP /

START controls

F2 fuse blown on power supply PCB

Check and change.

Frequency error (admits
45Hz

f main

65Hz)

(Ex10)

No 1L1

1L1 phase or frequence is out of

range

Check 1L1

1L1 phase and/or mains

frequence

Overload trip

(Ex11)

Excessive load or excessive current
during starting

Verify overload conditions during starting
time and steady state. Check settings in
parameters "Nxxx", "Lxxx", and "oxxx"

Synchronism loss

(Ex13)

Phase 1L1

1L1 lost

Check 1L1

1L1 phase

Short circuited thyristor

Check thyristor module.
Check ground connections and voltage to
ground.
Poor ribbon cable connection

Phase A, B, C thyristor

(Ex14)
(Ex15)
(Ex16)

No output phases

Check 2 T 1 , 4 T 2

2 T 1 , 4 T 2 and 6 T 3

6 T 3 phases

Heatsink thermostat

(Ex17)

Heatsink thermostat tripped by
overheating or defective

Check for adequate ventilation.
Check thermostat and wiring

Motor thermistor(Ex18)

Motor thermistor tripped by
overheating or defective

Check thermistor and wiring, if no
thermistor terminal 5 and 6 must be
jumpered

No input / output phases

Check power wire harness for 1L1,

1L1,

3 L 2 , 5 L 3 , 2 T 1 , 4 T 2

3 L 2 , 5 L 3 , 2 T 1 , 4 T 2 and 6 T 3

6 T 3

Phase A, B, C loss

(Ex19)
(Ex20)
(Ex21)

Defective thyristor or ribbon wire
harness loose or defective

Verify gate and cathode wire harness.
Verify thyristors

Stalled rotor

(Ex22)

Equipment detected stalled motor
rotor

Restart equipment and check for an
appreciable loss in motor speed at any
time

Internal error

(Ex23)

Micro-controller malfunction

Check IC1 and IC8 are correctly inserted
in their sockets.
Check for noise on control voltage power
or line

Long start time

(Ex25)

Current limit condition present more
than2 x ta sec. or 240 sec. (ta =
acceleration ramp time)

Increase current limit and / or acceleration
ramp time

Lock-out

(Ex27)

The time between startings is less
that the adjusted in parameter "LKxx"

Check if settings are correct.
This protection may be disabled

Undervoltage

(Ex28)

Overvoltage

(Ex29)

The line voltage exceeds of limit set in
parameters "UVxx" or "OVxx"

Check if settings are correct.
This protection may be disabled

Undercurrent

(Ex30)

Overcurrent

(Ex31)

The motor current exceeds of limit set
in parameters "UCxx" or "OCxx"

Check if settings are correct.
This protection may be disabled