DISASSEMBLY

sEctioN 6.1

maJor DisassEmBlY

Part 6

Page 153

4. Remove Stator Wires: Remove all wires from the voltage

regulator, remove the neutral and ground wires from

landing lugs, and remove N1 & N2 wires from main bea-

kers. See Figure 5.

5. Remove Control Wires: Remove Wires #N1,#N2, #0,

#15B, #23, GFCI Outlet, and unit status lights from the

control box. See Figure 6.

Figure 5.

Figure 6.

6. Remove controller mounting box: Using an 8mm socket

remove the two screws from the rear of the control-

ler mounting box. See Figure 7. Using a 10mm socket

remove the two bolts from under the front of the control-

ler mounting box. See Figure 8.

Figure 7.

Figure 8.

7. Remove engine intake baffle: Using a 10mm socket

remove the two bolts from the engine intake baffle. Pull

baffle toward you carefully, there are tabs holding the

backside of the baffle to the divider panel. See Figure 9.

Figure 9.