AC GENERATORS

sEctioN 2.3

trouBlEsHootiNG floWcHarts

Part 2

Page 39

STOP

TESTS

FREQUENCY O.K.,

BUT VOLTAGE LOW

TEST 14 - CHECK

AC OUTPUT

FREQUENCY

TEST 15 - ADJUST

ENGINE GOVERNOR

TEST 16 - CHECK

STEPPER MOTOR

CONTROL

TEST 2 - CHECK

AC OUTPUT

VOLTAGE

TEST 17 - ADJUST

VOLTAGE

REGULATOR

TEST 9 -

CHECK

CAPACITOR

LOW

LOW -

SINGLE CYLINDER

UNITS

LOW -

V-TWIN UNITS

FREQUENCY O.K.,

BUT VOLTAGE IS

STILL LOW

GO TO “PROBLEM 1” FLOW CHART -
START AT “TEST 4 - F/E”

GO TO “PROBLEM 2”

VOLTAGE AND FREQUENCY O.K.

8/10 kW UNITS

8/10 kW UNITS

NO VOLTAGE

GO TO TEST 4

GO TO “PROBLEM 2”

8/10 kW UNITS

12-20 kW UNITS

12-20 kW UNITS

12-20 kW UNITS

FREQUENCY AND

VOLTAGE O.K.

Problem 3 - Generator Produces Low Voltage at No-Load

STOP

TESTS

Problem 4 - Generator Produces High Voltage at No-Load

TEST 14 - CHECK

AC OUTPUT

FREQUENCY

TEST 15 - ADJUST

ENGINE GOVERNOR

TEST 16 - CHECK

STEPPER MOTOR

CONTROL

TEST 2 - CHECK

AC OUTPUT

VOLTAGE

HIGH

HIGH -

SINGLE CYLINDER

UNITS

HIGH -

V-TWIN UNITS

REPLACE DEFECTIVE
VOLTAGE REGULATOR

FREQUENCY AND

VOLTAGE O.K.

TEST 17 - ADJUST

VOLTAGE

REGULATOR

TEST 9 -

CHECK

CAPACITOR

8/10 kW UNITS

12-20 kW UNITS

FREQUENCY O.K.,

BUT VOLTAGE IS

STILL HIGH

FREQUENCY O.K.,

BUT VOLTAGE HIGH

VOLTAGE AND FREQUENCY O.K.

GO TO “PROBLEM 2”

8/10 kW UNITS

12-20 kW UNITS