3 non-prepackaged interconnections, Part 1, Non-prepackaged interconnections – Generac Power Systems 8 kW LP User Manual

Page 16

Advertising
background image

Page 14

Part 1

General information

Section 1.3

non-PrePackaged interconnectionS

Discussion:
on the current model air-cooled generators Wire 194
was changed to 15B. Wire 15B is still utilized for posi-
tive voltage for the transfer relay and Wire 23 is still the
control ground for transferring the generator. By follow-
ing the procedures below it is possible to connect new
product with Wire 15B to old or current product that
still utilize Wire 194, such as an rts switch.

ConneCt a pre-2008 load Center switCh to a

Current or Future air-Cooled generator.

ProceDure:

1. Follow all instructions located in the Installation Manual

that was supplied with the unit regarding mounting of the

switch, junction box, and generator.

note: when installing a standalone 5500 series
generator, the battery charger will be located in the
generator on the side of the control assembly.

2. Inside the Junction box between the generator and the

transfer switch there will be 5 wires coming from the

generator and 4 wires from the transfer switch.

3. Using the following diagram and UL approved wire nuts

connect the following wires together. Wire 0 will not be

utilized for this setup.

WIRE NUTS

N1 (BLU)

N2 (YEL)

23 (BRN)

194 (ORG)

N1 (YEL)

N2 (YEL)

23 (WHT)

15B (RED)

0 (BLK)

CONTROL WIRES FROM

ENGINE GENERATOR

CONTROL WIRES FROM

TRANSFER SWITCH

Figure 1. Wire Connections

WIRE
NUTS

N1 (BLU)

N2 (YEL)

23 (BRN)

194 (ORG)

N1 (YEL)

N2 (YEL)

23 (WHT)

15B (RED)

0 (BLK)

CONTROL WIRES FROM ENGINE GENERATOR

“08” & LATER HSB AIR-COOLED GENERATORS

SINGLE & V-TWIN ENGINES

PRE “08” LOAD CENTER

TRANSFER SWITCH

EXTERNAL CUSTOMER

CONNECTION BOX

INSTALL BATTERY CHARGER GENERAC P/N 0G8023

CONTROL WIRES FROM TRANSFER SWITCH

Figure 2. Post 2008 HSB Interconnections