Generac Power Systems 8 kW LP User Manual

Page 53

Advertising
background image

STEPPER MOTOR

PULL ARM THIS
DIRECTION TO
CLOSE THROTTLE

Figure 11. Throttle Positions 9/10 kW Units

STEPPER MOTOR

STEPPER MOTOR ARM

PULL ARM THIS
DIRECTION TO
CLOSE THROTTLE

Figure 12. Throttle Positions 9/10 kW Units

STEPPER MOTOR

STEPPER MOTOR ARM

PULL ARM THIS
DIRECTION TO
CLOSE THROTTLE

Figure 13. Throttle Positions 12-20 kW Units

RED

EMPTY

YELLOW

BROWN

ORANGE

BLACK

Figure 14. Six Pin Connector Wire Colors

teSt 17 – check and adjuSt VoltaGe

reGulator (12-20 kW)

DISCUSSION:

For additional information, refer to description and
components Section 2.1.

PROCEDURE (V-TWIN ENGINE UNITS):
With the frequency at 60 Hertz, slowly turn the
slotted potentiometer (Figure 15) until line voltage
reads 247-249 volts.
note: the access panel on top of the control panel
must be removed to adjust the voltage regulator.
note: the voltage regulator is housed in the
back of the generator control panel. the regula-
tor maintains a voltage in direct proportion to
frequency at a 2-to-1 ratio. For example, at 60
hertz, line-to-neutral voltage will be 120 volts.

Figure 15. Voltage Adjustment Potentiometer

RESULTS:
1. If the frequency and voltage are now good, discontinue tests.
2. If frequency is now good but voltage is high or low, refer

back to flow chart.

Page 51

AC GENERATORS

sEctioN 2.4

DiaGNostic tEsts

Part 2

Advertising
This manual is related to the following products: